Ademco 4110XMP/First Alert FA-120C Program Sheet

Version Info v6 and above are capable of paging and duress is user code 8

Main chip on panel should show N7185V3 (V3 and above is v6 or higher)

Enter Program 1. Master Code + 8 + 0 + 0 (Display should show 00)

or

2. Power down then back up and press * and # within 1 minute

Move to Location * + Location

View Location # + Location (Display will read off one digit at a time)

Exit Program 1. *98 exits and does not allow re-entry to programming without cycling power and pressing * and #

or

2. *99 exits and does allow re-entry by Installer Code + 8 + 00

Programming can be re-entered up to 1 minute after exiting with * and # (# + 0 disables this feature)

Default Panel *97

Compatibility

Power Ratings 500ma Aux output

2A Siren output

Send to 1. Exit programming

Downloader 2. Press Installer or Master Code + # + 1

3. "CC" or "MODEM COMM" appears for approx. 2 minutes

4. Display will return to normal once upload is finished

Keypad Address (6128/6150 keypads)

  1. Remove power from keypad then power back up

  2. Hold 1 & 3 for 3 seconds, "ADDR = XX" or "XX" should appear (XX = current address)

  3. Within 10 seconds enter 00 to erase old address then enter new address (31)

  4. Press * to save and exit

(6150RF keypads)

  1. Power keypad down then back up

  2. Hold 1 & 3 for 3 seconds until flashing " - - 0 0" (if "DA" shows power down then up again)

  3. Press 1 and "cA XX" should appear (XX = current address)

  4. Press 31 then * to exit back to flashing " -- 0 0"

4. Press * to exit

Go-No Go Test (Verifies adequate RF by reducing receiver signal strength by 50%)

  1. Installer Code + # + 4

  2. a. Siren sounds

b. Panel may send walk test signal (If test signal was programmed)

c. "dd" appears on screen

d. Keypad will beep every 15 seconds

  1. Fault sensor, keypad should beep 3 times and display zone number,

if no beeps sound reorient or move sensor a few inches and try again

  1. Exit with Installer Code + 1 (OFF)

Hex Program Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15

  1. = Enable

  1. = Enable

  1. = Enable

  1. to 31 if using 5700 Wireless sensors

90 If using 4219 Hardwire Zone Expander

  1. = Enable

  1. = Enable

  1. = Enable

  1. = 8 minutes

  2. = 12 minutes

  3. = 16 minutes

  1. = Entry/Exit

  1. = Instant/Perimeter

  1. = Trouble by Day

7 = 24 hr Audible (Police Panic)

(Hardwire smoke detectors must use this zone) 9 = Fire without timeout

10 = Interior Delay (Not available on older 4110XMP's)

  1. = Fire Panic

6 = Silent Panic

7 = Audible Panic

8 = 24 hr Auxiliary (Medical)

9 = Fire without Timeout

Exit Delay = Entry + 15 seconds 2 = 30 seconds

3 = 45 seconds

4 = 60 seconds

  1. = 90 seconds

  1. = 10ms

End Phone with * # + 11 = * # + 12 = # # + 13 = 2.5 second pause

Note: Pager not available on older 4110XMP's, pager will not work if Account starts with 0

(Hex B = #+11 C = #+12 D = #+13 E = #+14 F = #+15)

  1. = 3/1, 4/1 Radionics Standard

  2. = 4/2 Ademco L/S Standard

  3. = 4/2 Radionics Standard

6 = 4/2 Ademco Express

7 = Contact ID

8 = 3/1, 4/1 Ademco L/S Expanded

9 = 3/1, 4/1 Radionics Expanded

  1. = DTMF Dialing

  2. = Pulse Dialing, CS on Watts Line

  3. = DTMF Dialing, CS on Watts Line

  1. = Sescoa

  1. = Enable

  1. = 24 Hours

  2. = Weekly

To Primary Phone To Secondary Phone

0 = All Reports Backup Only

  1. = Alarms, Restore, Cancel All Other Reports

  2. = All Reports except Open/Close, Test Open/Close, Test

  3. = Alarms, Restore, Cancel All Reports

  4. = All Reports except Open/Close, Test All Reports

  5. = All Reports (Dual Reporting) All Reports

The following is only available with very new 4110XM's, use 6 if programming Pagers

  1. = All reports except Open/Close Alarms, Open/Close, Troubles

  2. = All reports Alarms, Troubles

  3. = All reports Alarms, Open/Close, Troubles

  4. = All reports except Open/Close Alarms, Open/Close for Users 5-25, Troubles

(Not available on older 4110XMP's) I _1 _I 3 & # (Audible Panic, sends 96)

Wireless Zone Programming

I _ 1 _I _0 I Report Code Zone 14 to 29 = Instant

Zone 30 to 47 = Interior/PIR

I _ 1 _I _0 I Report Code Zone 56 to 61 = Day Zone

Zone 62 = 24 hr Audible

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

I _ 1 _I _0 I Report Code

  1. = Unlimited

#15 = Answer Machine over-ride