Ademco 4120EC Program Sheet

Information 4/2, this panel CANNOT report Contact ID format

Signals Zone 1 31 (11 if Fire) 3 & # Panic 40

Zone 2 32 * & # Panic 2B

Zone 3 33 Fire Trouble 71

Zone 4 34 Fire Restore E1

Zone 5 35 AC Fail 79

Zone 6 36 Low Battery 78

Zone 7 37 Openings 51 to 58

Zone 8 38 Closings 61 to 68

Duress 29 Cancel D0

Enter Program 1. 4120 + 8 + 0 + 0 (Display should show 00)

or

2. Power down then back up and press * and # within 1 minute

Move to Location * + Location

View Location # + Location (Display will read off one digit at a time)

Exit Program 1. *98 exits and does not allow re-entry to programming without cycling power and pressing * and #

or

2. *99 exits and does allow re-entry by Installer Code + 8 + 00

Programming can be re-entered up to 1 minute after exiting with * and # (# + 0 disables this feature)

Default Panel *96

Compatibility

Power Ratings 700ma Aux output

2.8A Siren output

Send to 1. Exit programming

Downloader 2. Press Installer or Master Code + # + 1

3. "CC" or "MODEM COMM" appears for approx. 2 minutes

4. Display will return to normal once upload is finished

Keypad Address (6128/6150 keypads)

  1. Remove power from keypad then power back up

  2. Hold 1 & 3 for 3 seconds, "ADDR = XX" or "XX" should appear (XX = current address)

  3. Within 10 seconds enter 00 to erase old address then enter new address (31)

  4. Press * to save and exit

(6150RF keypads)

  1. Power keypad down then back up

  2. Hold 1 & 3 for 3 seconds until flashing " - - 0 0" (if "DA" shows power down then up again)

  3. Press 1 and "cA XX" should appear (XX = current address)

  4. Press 31 then * to exit back to flashing " -- 0 0"

4. Press * to exit

Hex Program Hex A = 10 B = 11 C = 12 D = 13 E = 14 F = 15

Use Caution, this panel allows you into locations that are not on the program sheet

I _0 _I _1 _I Zone 2 00 = Disabled

I _0 _I _3 _I Zone 3 01 = Entry/Exit

I _0 _I 4 _I Zone 4 02 = Not Used

I _0 _I _5 _I Zone 5 03 = Instant

I _0 _I _6 _I Zone 6 04 = Interior Follower

I _0 _I _7 _I Zone 7 05 = Trouble by Day/Alarm by Night

I _0 _I _8 _I Zone 8 06 = 24 Hour Silent (Holdup)

07 = 24 Hour Audible (Police)

I _0 _I _7 _I 3 & # 09 = Fire

I _0 _I _6 _I * & #

I _1 _I Zone 2 1 = Normally Closed

I _1 _I Zone 3

I _1 _I Zone 4 (0 if Smoke on Zone 1)

I _1 _I Zone 5

I _1 _I Zone 6

I _1 _I Zone 7

I _1 _I Zone 8

  1. = 10ms

  1. = No Fire Timeout on siren

Express Format 1 = Enable

  1. = 12 Hours

  2. = 24 Hours

  3. = 168 Hours (Week)

  1. = Enable

  1. = Touch-Tone Dial

(Example 9 is 09*)

(Example 1234 is 01 02 03 04) Hex B = 11 C = 12 D = 13 E = 14 F = 15

(12 digits, end with *) # + 11 = * # + 12 = # # + 13 = 2.5 second pause

(15's Default CSID to Factory)

  1. = No EOL resistors

  1. to 15 Rings to answer

15 = Answer Machine Over-Ride

  1. = Radionics

  2. = 4/2 Ademco Express

  1. = Radionics

  2. = 4/2 Ademco Express

  1. = Enable

  1. = Enable

  1. = Extended

  1. = Extended

  1. = Extended

  1. = Extended

  1. = Extended

  1. = Extended

I _0 _I _3 _I Zone 2 (Sends 32)

I _0 _I _3 _I Zone 3 (Sends 33)

I _0 _I _3 _I Zone 4 (Sends 34)

I _0 _I _3 _I Zone 5 (Sends 35)

I _0 _I _3 _I Zone 6 (Sends 36)

I _0 _I _3 _I Zone 7 (Sends 37)

I _0 _I _3 _I Zone 8 (Sends 38)

I _0 _I _4 _I 3 & # (Zone A/Medical or Fire) (Sends 40)

I _0 _I _2 _I * & # (Zone B/Police) (Sends 2B)

I _0 _I _9 _I AC Loss 2nd Digit (Sends 79)

I _0 _I _7 _I Trouble (Fire) (Sends 71)

I _1 _I _4 _I Trouble Restore (Fire) (Sends E1)

I _0 _I _0 _I Bypass (Not used)

I _0 _I _0 _I Bypass Restore (Not used)

I _0 _I _0 _I Alarm/AC/Low Bat Restore (Not used)

I _0 _I _0 _I Closings (06 If needed)

I _0 _I _7 _I Low Battery

I _0 _I _8 _I Low Battery 2nd Digit (Sends 78)

I _0 _I _0 _I Test (Not used)

I _1 _I _3 _I Cancel (Sends D0)

Honeywell Compass downloader screens