Ademco 5140XM/First Alert FA1500C Program Sheet

Enter Program 1. 5140 + 8 + 0 + 0 (Display should show 00)

or

2. Power down then back up and press * and # within 1 minute

Move to Location * + Location

View Location # + Location (Display will read off one digit at a time)

Exit Program 1. *98 exits and does not allow re-entry to programming without cycling power and pressing * and #

or

2. *99 exits and does allow re-entry by Installer Code + 8 + 00

Programming can be re-entered up to 1 minute after exiting with * and # (# + 0 disables this feature)

Default Panel *97

Compatibility

Power Ratings 1A Aux output

2.3A Siren output

Device Address All keypads, receivers and expanders must be addressed and added in #93 menu

Address 00 and 01 are pre-programmed as alpha keypads

Address first keypad as 00 to allow entry into programming

00 Alpha Keypad (cannot be changed)

  1. to 30 Keypads, zone expanders, wireless receivers etc

Keypad Address (6128/6139/6150/6160 keypads)

  1. Remove power from keypad then power back up

  2. Hold 1 & 3 for 3 seconds, "ADDR = XX" or "XX" should appear (XX = current address)

  3. Within 10 seconds enter 00 to erase old address then enter new address (00 to 30)

  4. Press * to save and exit

(6128RF/6150RF keypads)

  1. Power keypad down then back up or remove backplate

  2. Within 30 seconds hold 1 & 3 for 3 seconds until flashing " - - 0 0 "

  3. Press 1 and "cA XX" should appear (XX = current address)

  4. Enter new address (00 to 30) then * to exit back to flashing " -- 0 0 "

  5. Press * to exit

Sniffer Test (Tests wireless sensors)

  1. Installer Code + # + 3

  2. Keypad displays all wireless sensors, faulting sensor removes it from list

  3. Exit with Installer Code + 1 (OFF)

Go-No Go Test (Verifies adequate RF by reducing receiver signal strength by 50%)

  1. Installer Code + # + 4

  2. a. Siren sounds

b. Panel may send walk test signal (If test signal was programmed)

c. "dd" appears on screen

d. Keypad will beep every 15 seconds

  1. Fault sensor, keypad should beep 3 times and display zone number,

if no beeps sound reorient or move sensor a few inches and try again

  1. Exit with Installer Code + 1 (OFF)

Hex Program Hex A = # + 10 B = # + 11 C = # + 12 D = # + 13 E = # + 14 F = # + 15

#93 Menu

All Zone programming is done by # 93 menu, enter #93 for below menu (Click to go to section)

Tech_201000000129.gif 1 enters, 0 moves to next menu (Alpha Programming)

Tech_201000000130.gif 1 enters, 0 moves to next menu (Device Programming)

Tech_201000000131.gif 1 enters, 0 moves to next menu (Exit #93 Menu)

Tech_201000000132.gif 1 exits #93 menu, 0 moves back to Zone Program

l__?__l__?__l Zone 1 l__?__l__?__l Zone 9 00 = Disabled

l__?__l__?__l Zone 2 l__?__l__?__l Zone 10 01 = Entry/Exit 1

l__?__l__?__l Zone 3 l__?__l__?__l Zone 11 02 = Entry/Exit 2

l__?__l__?__l Zone 4 l__?__l__?__l Zone 12 03 = Instant

l__?__l__?__l Zone 5 l__?__l__?__l Zone 13 04 = Interior

l__?__l__?__l Zone 6 l__?__l__?__l Zone 14 05 = Day Zone

l__?__l__?__l Zone 7 l__?__l__?__l Zone 15 06 = Silent Holdup

l__?__l__?__l Zone 8 l__?__l__?__l Zone 16 07 = Audible Police

08 = 24 Hour Auxiliary

l__?__l__?__l Zone 17 l__?__l__?__l Zone 25 10 = Interior with Delay

l__?__l__?__l Zone 18 l__?__l__?__l Zone 26 16 = Fire with Verification

l__?__l__?__l Zone 19 l__?__l__?__l Zone 27 17 = Fire Water Flow

l__?__l__?__l Zone 20 l__0__l__ 0__l Not Used 18 = Fire Supervisory

l__?__l__?__l Zone 21 l__0__l__ 0__l Zone 97 Polling LP 19 = 24 Hour Trouble

l__?__l__?__l Zone 22 l__0__l__ 9__l Zone 95 1 & *

l__?__l__?__l Zone 23 l__0__l__ 8__l Zone 96 3 & #

l__?__l__?__l Zone 24 l__0__l__ 7__l Zone 99 * & #

  1. = Arms/Disarms/Silences Alarms

  2. = Silences only if Fire Alarm

  1. = Enable

  1. = Enable

  1. = Enable

  1. = Randomize 10 - 40 minutes

  2. = Randomize 6 - 12 Hours

  1. = Enable

  1. = Enable

  1. = Enable

  1. = No Report if other Reports Sent

  1. to 199 Hours

  1. = Enable

  1. = Enable

  1. = Touch-Tone Dial

(Example 9 is 09* )

(Example 1234 is 01 02 03 04) Hex B = 11 C = 12 D = 13 E = 14 F = 15

(17 digits, end with * ) # + 11 = * # + 12 = # # + 13 = 2.5 second pause

(15's Default CSID to Factory)

l__1_ l System Shutdown 1 = Enable

l__0 _l Not Used

l__1_ l Remote Bypass

l__1_ l Remote Disarm

l__1_ l Remote Arm

l__1_ l Upload Programming

l__1_ l Download Programming

  1. to 64 = Zone 01 to 64

  1. = Enable

  1. = Enable

  1. = Normally Closed

  1. = 11 seconds

  2. = 30 seconds

  1. = Wait for True Dial Tone

  1. to 14 = Rings before answer

15 = Answering Machine over-ride

  1. = Contact ID

  2. = Ademco High Speed

  3. = Ademco Express

  1. = Sescoa/Radionics

  1. = Contact ID

  2. = Ademco High Speed

  3. = Ademco Express

  1. = Sescoa/Radionics

  1. = Enable

  1. = Sescoa

  1. = Enable

for Primary l__0__l Restore 1 = Expanded

l__0__l Bypass

l__0__l Trouble

l__0__l Open/Close

l__0__l Low Bat/Walk Test

for Secondary l__0__l Restore 1 = Expanded

l__0__l Bypass

l__0__l Trouble

l__0__l Open/Close

l__0__l Low Bat/Walk Test

l__0__l__1__l Zone 1 l__0__l__1__l Zone 1

l__0__l__1__l Zone 2 l__0__l__1__l Zone 2

l__0__l__1__l Zone 3 l__0__l__1__l Zone 3

l__0__l__1__l Zone 4 l__0__l__1__l Zone 4

l__0__l__1__l Zone 5 l__0__l__1__l Zone 5

l__0__l__1__l Zone 6 l__0__l__1__l Zone 6

l__0__l__1__l Zone 7 l__0__l__1__l Zone 7

l__0__l__1__l Zone 8 l__0__l__1__l Zone 8

l__0__l__1__l Zone 9 l__0__l__1__l Zone 9

l__0__l__1__l Zone 10 l__0__l__1__l Zone 10

l__0__l__1__l Zone 11 l__0__l__1__l Zone 11

l__0__l__1__l Zone 12 l__0__l__1__l Zone 12

l__0__l__1__l Zone 13 l__0__l__1__l Zone 13

l__0__l__1__l Zone 14 l__0__l__1__l Zone 14

l__0__l__1__l Zone 15 l__0__l__1__l Zone 15

l__0__l__1__l Zone 16 l__0__l__1__l Zone 16

l__0__l__1__l Alarm/Supervision Restore

l__0__l__1__l Trouble

l__0__l__1__l Trouble Restore

l__0__l__0__l Bypass

l__0__l__0__l Bypass Restore

l__0__l__1__l Zone 17 l__0__l__1__l Zone 17

l__0__l__1__l Zone 18 l__0__l__1__l Zone 18

l__0__l__1__l Zone 19 l__0__l__1__l Zone 19

l__0__l__1__l Zone 20 l__0__l__1__l Zone 20

l__0__l__1__l Zone 21 l__0__l__1__l Zone 21

l__0__l__1__l Zone 22 l__0__l__1__l Zone 22

l__0__l__1__l Zone 23 l__0__l__1__l Zone 23

l__0__l__1__l Zone 24 l__0__l__1__l Zone 24

l__0__l__1__l Zone 25 l__0__l__1__l Zone 25

l__0__l__1__l Zone 26 l__0__l__1__l Zone 26

l__0__l__1__l Zone 27 l__0__l__1__l Zone 27

l__0__l__1__l Zone 28 l__0__l__1__l Zone 28

l__0__l__1__l Zone 29 l__0__l__1__l Zone 29

l__0__l__1__l Zone 30 l__0__l__1__l Zone 30

l__0__l__1__l Zone 31 l__0__l__1__l Zone 31

l__0__l__1__l Zone 32 l__0__l__1__l Zone 32

l__0__l__1__l Alarm/Supervision Restore

l__0__l__1__l Trouble

l__0__l__1__l Trouble Restore

l__0__l__0__l Bypass

l__0__l__0__l Bypass Restore

l__0__l__1__l Zone 33 l__0__l__1__l Zone 33

l__0__l__1__l Zone 34 l__0__l__1__l Zone 34

l__0__l__1__l Zone 35 l__0__l__1__l Zone 35

l__0__l__1__l Zone 36 l__0__l__1__l Zone 36

l__0__l__1__l Zone 37 l__0__l__1__l Zone 37

l__0__l__1__l Zone 38 l__0__l__1__l Zone 38

l__0__l__1__l Zone 39 l__0__l__1__l Zone 39

l__0__l__1__l Zone 40 l__0__l__1__l Zone 40

l__0__l__1__l Zone 41 l__0__l__1__l Zone 41

l__0__l__1__l Zone 42 l__0__l__1__l Zone 42

l__0__l__1__l Zone 43 l__0__l__1__l Zone 43

l__0__l__1__l Zone 44 l__0__l__1__l Zone 44

l__0__l__1__l Zone 45 l__0__l__1__l Zone 45

l__0__l__1__l Zone 46 l__0__l__1__l Zone 46

l__0__l__1__l Zone 47 l__0__l__1__l Zone 47

l__0__l__1__l Zone 48 l__0__l__1__l Zone 48

l__0__l__1__l Alarm/Supervision Restore

l__0__l__1__l Trouble

l__0__l__1__l Trouble Restore

l__0__l__0__l Bypass

l__0__l__0__l Bypass Restore

l__0__l__1__l Zone 49 l__0__l__1__l Zone 49

l__0__l__1__l Zone 50 l__0__l__1__l Zone 50

l__0__l__1__l Zone 51 l__0__l__1__l Zone 51

l__0__l__1__l Zone 52 l__0__l__1__l Zone 52

l__0__l__1__l Zone 53 l__0__l__1__l Zone 53

l__0__l__1__l Zone 54 l__0__l__1__l Zone 54

l__0__l__1__l Zone 55 l__0__l__1__l Zone 55

l__0__l__1__l Zone 56 l__0__l__1__l Zone 56

l__0__l__1__l Zone 57 l__0__l__1__l Zone 57

l__0__l__1__l Zone 58 l__0__l__1__l Zone 58

l__0__l__1__l Zone 59 l__0__l__1__l Zone 59

l__0__l__1__l Zone 60 l__0__l__1__l Zone 60

l__0__l__1__l Zone 61 l__0__l__1__l Zone 61

l__0__l__1__l Zone 62 l__0__l__1__l Zone 62

l__0__l__1__l Zone 63 l__0__l__1__l Zone 63

l__0__l__1__l Zone 64 l__0__l__1__l Zone 64

l__0__l__1__l Alarm/Supervision Restore

l__0__l__1__l Trouble

l__0__l__1__l Trouble Restore

l__0__l__0__l Bypass

l__0__l__0__l Bypass Restore

l__0__l__0__l Not Used l__0__l__0__l Not Used

l__0__l__0__l Not Used l__0__l__0__l Not Used

l__0__l__0__l Not Used l__0__l__0__l Not Used

l__0__l__1__l Duress l__0__l__1__l Duress

l__0__l__1__l Zone 97 (Polling Loop Short) l__0__l__1__l Zone 97 (Polling Loop Short)

l__0__l__1__l Zone 95 (1 & *) l__0__l__1__l Zone 95 (1 & *)

l__0__l__1__l Zone 96 (3 & #) l__0__l__1__l Zone 96 (3 & #)

l__0__l__1__l Zone 99 (* & #) l__0__l__1__l Zone 99 (* & #)

l__0__l__1__l Alarm/Supervision Restore

l__0__l__1__l Trouble

l__0__l__1__l Trouble Restore

l__0__l__0__l Bypass

l__0__l__0__l Bypass Restore

l__0__l Zone Type 1 (Entry/Exit 1) 0 = No Restoral Report

l__0__l Zone Type 2 (Entry Exit 2) 1 = Restoral Report

l__0__l Zone Type 3 (Perimeter)

l__0__l Zone Type 4 (Interior Follower)

l__0__l Zone Type 5 (Day/Night)

l__0__l Zone Type 6 (24 Hour Silent)

l__0__l Zone Type 7 (24 Hour Audible)

l__0__l Zone Type 8 (24 Hour Auxiliary)

l__1__l Zone Type 9 (Fire without Verification) 0 = No Restoral Report

l__0__l Zone Type 10 (Interior Delay) 1 = Restoral Report

l__0__l__0__l Close l__0__l__0__l Open

l__0__l__0__l Open l__0__l__0__l Close

l__1__l__1__l Low Battery l__0__l__0__l Low Battery

l__0__l__0__l Low Battery Restore l__0__l__0__l Low Battery Restore

l__1__l__1__l AC Loss l__0__l__0__l AC Loss

l__1__l__1__l AC Restore l__0__l__0__l AC Restore

l__1__l__1__l Communicator Test l__0__l__0__l Communicator Test

l__0__l__0__l Power Up l__0__l__0__l Power Up

l__1__l__1__l Cancel l__0__l__0__l Cancel

l__0__l__0__l Program Tamper l__0__l__0__l Program Tamper

Day Hour Minutes

  1. to 15 = 01 to 15 Alarms

  1. = Continuous

  1. = 16 seconds

  1. = At Bell Timeout

  2. = At Disarm

Hex B = 11, C = 12, D = 13, E = 14, F = 15

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

To access 2nd Level of Programming press *94 then enter * + 2-digits, to exit back to 1st Level enter *99

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

  1. *01 Zone Types for Zones 28 to 32 1*02 Zone Types for Zones 33 to 40

l__?__l__?__l Zone 28 l__?__l__?__l Zone 33 00 = Disabled

l__?__l__?__l Zone 29 l__?__l__?__l Zone 34 01 = Entry/Exit 1

l__?__l__?__l Zone 30 l__?__l__?__l Zone 35 02 = Entry/Exit 2

l__?__l__?__l Zone 31 l__?__l__?__l Zone 36 03 = Instant

l__?__l__?__l Zone 32 l__?__l__?__l Zone 37 04 = Interior

l__?__l__?__l Zone 38 05 = Day Zone

l__?__l__?__l Zone 39 06 = Silent Holdup

l__?__l__?__l Zone 40 07 = Audible Police

08 = 24 Hour Auxiliary

  1. *03 Zone Type for Zone 41 to 48 1*04 Zone Types for Zone 49 to 56 09 = Fire w/o Verification

l__?__l__?__l Zone 41 l__?__l__?__l Zone 49 10 = InteriorDelay

l__?__l__?__l Zone 42 l__?__l__?__l Zone 50 16 = Fire w/Verification

l__?__l__?__l Zone 43 l__?__l__?__l Zone 51 17 = Fire Water Flow

l__?__l__?__l Zone 44 l__?__l__?__l Zone 52 18 = Fire Supervisory

l__?__l__?__l Zone 45 l__?__l__?__l Zone 53 19 = 24 Hour Trouble

l__?__l__?__l Zone 46 l__?__l__?__l Zone 54

l__?__l__?__l Zone 47 l__?__l__?__l Zone 55

l__?__l__?__l Zone 48 l__?__l__?__l Zone 56

  1. *05 Zone Type for Zone 57 to 64

l__?__l__?__l Zone 57

l__?__l__?__l Zone 58

l__?__l__?__l Zone 59

l__?__l__?__l Zone 60

l__?__l__?__l Zone 61

l__?__l__?__l Zone 62

l__?__l__?__l Zone 63

l__?__l__?__l Zone 64

  1. *33 Touch-Tone with Rotary Backup l__1 _l 0 = Disable

  1. = Enable

  1. *34 Comm Split Report Selection l__0 _l 0 = Disable

  1. = Alarms Primary, others Secondary

  2. = O/C/Test Secondary, others Primary

  1. *40 System Non-Alarm Codes 1st Digit 1*41 System Non-Alarm Codes 2nd Digit

I _ I _ _I Armed Stay I _ I _ _I Armed Stay

I _ I _ _I Time Set/Event Log Reset I _ I _ _I Time Set/Event Log Reset

I _ I _ _I Event Log 50 & 90% Full I _ I _ _I Event Log 50 & 90% Full

I _ I _ _I Event Log Overflow I _ I _ _I Event Log Overflow

  1. *43 Perm Keypad Backlight l__1 _l 0 = Disable

  1. = Enable

  1. *45 Exit Delay Sounder l__1 _l 1 = Enable

0 = Disable

  1. *47 Chime Annunciation on Bell 1 l__1 _l 0 = Disable

  1. = Enable

  1. *52 Cancel Report Restriction l__1 _l 0 = No Restriction

  1. = Within Bell Timeout

  1. *53 Download Callback l__1 _l 0 = Callback Required

  1. = No Callback

  1. *70 Event Log Types l__1 _l Alarm 0 = Disable Logging

l__1 _l Check 1 = Enable Logging

l__1 _l Bypass

l__1 _l O/C

l__1 _l System

  1. *71 12/24 Hour Time Stamp Format l__0 _l 0 = 12 Hour

  1. = 24 Hour (Military)

  1. *72 Event Log Printer On-line Mode l__0 _l 0 = Disable

  1. = Enable

  1. *73 Printer Baud Rate l__0 _l 0 = 1200 Baud

  1. = 300 Baud

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

To access 3rd Level of Programming press *94 then enter * + 2-digits, to exit back to 2nd Level enter *99

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

3*10 Response Type Assignment

l__1 _l__9 _l Zone 70 Bell 1 19 = 24 Hour Trouble

l__0 _l__0 _l Zone 71 Bell 2

l__0 _l__0 _l Zone 72 Earth Ground

l__0 _l__0 _l Zone 73 J2/In 1

l__0 _l__0 _l Zone 74 Dialer 1

l__0 _l__0 _l Zone 75 Dialer 2

l__0 _l__0 _l Not Used

l__0 _l__0 _l Not Used

3*15 Alarm Bell Sound l__0 _l Bell 1 0 = Pulsed

l__0 _l Bell 2 1 = Steady

3*16 Delay for Zone Types 17 & 18 l__0 _l__0 _l 00 to 15 x2 seconds

(Waterflow & Fire Supervision)

3*17 Alt Function (Tamper) for Zone 6 l__0 _l__0 _l 0 = Disabled

  1. = Enabled

3*19 Enable J2 Header Printer Port l__0 _l 0 = Pins 5 & 9 function per 3*20

  1. = Pins 5 & 9 as printer RXD & DTR

3*20 Trigger Outputs Selection l__0 _l 0 = Lorra Full Connection

  1. = Lorra Limited Connection/Keyswitch

  2. = Lorra Fire Connection & 5140LED

  3. *21 Max # of Dialer Retries l__8 _l 1 to 8 attempts

3*30 Dialer Selection l__1 _l Main 0 = Disabled

l__0 _l Backup 1 = Enabled

3*31 Backup Dialer Touch-Tone/Rotary l__0 _l 0 = Rotary

  1. = Touch-Tone

3*40 Report Codes for Zone 70 to 77 3*41 ID Digits for Zones 70-77

l__0 _l__1 _l Zone 70 l__0 _l__1 _l Zone 70

l__0 _l__1 _l Zone 71 l__0 _l__1 _l Zone 71

l__0 _l__1 _l Zone 72 l__0 _l__1 _l Zone 72

l__0 _l__1 _l Zone 73 l__0 _l__1 _l Zone 73

l__0 _l__1 _l Zone 74 l__0 _l__1 _l Zone 74

l__0 _l__1 _l Zone 75 l__0 _l__1 _l Zone 75

l__0 _l__1 _l Zone 76 l__0 _l__1 _l Zone 76

l__0 _l__1 _l Zone 77 l__0 _l__1 _l Zone 77

3*42 Alarms/Restorals for Zone 70 to 77

l__0 _l__0 _l Alarm/Restorals

l__0 _l__0 _l Trouble

l__0 _l__0 _l Trouble Restore

l__0 _l__0 _l Bypass

l__0 _l__0 _l Bypass Restore

3*50 Zone Type Restore Enable Zn 16 to 18 l__1 _l Zone Type 16 0 = Disable

l__1 _l Zone Type 17 1 = Enable

16 = Fire w/Verification l__1 _l Zone Type 18

17 = Fire Water Flow

18 = Fire Supervisory

3*51 Non Alarm Codes 1st Digit 3*52 Non Alarm Codes 2nd Digit

l__1 _ l__1 _l Fire/Burg Walk Test Start l__0 _ l__0 _l Fire/Burg Walk Test Start

l__1 _ l__1 _l Fire/Burg Walk Test End l__0 _ l__0 _l Fire/Burg Walk Test End

3*57 Bell 2/Aux Relay Confirm Am Ding l__0 _l Bell 2 0 = Disable

l__0 _l Aux 1 = Enable

3*58 Bell 2/Aux Relay AC Loss Alarm l__0 _l Bell 2 0 = Disable

l__0 _l Aux 1 = Enable

3*59 Bell 2/Aux Relay Chime Annunciation l__0 _l Bell 2 0 = Disable

l__0 _l Aux 1 = Enable

3*60 Bell 2/Aux Relay Timeout l__0 _ l__0 _l Bell 2 0 = Disable

l__0 _ l__0 _l Aux 1 = Enable

3*61 Aux Relay Function l__0 _ l__0 _l Bell 2 0 = Trouble/Supervisory

  1. = Alarm/Silenced by Code + OFF

  2. = Smoke Detector Reset

  3. = Battery Save

  4. = Alarm, Silenced by Code + # + 67

3*70 Bell 1 & 2 Aux Relay Activation Zone 1 to 8

l__1 _l Zone 1 0 = None

l__1 _l Zone 2 1 = Bell 1

l__1 _l Zone 3 2 = Bell 2

l__1 _l Zone 4 3 = Bell 1 & 2

l__1 _l Zone 5 4 = Aux Relay

l__1 _l Zone 6 5 = Bell 1 & Relay

l__1 _l Zone 7 6 = Bell 2 & Relay

l__1 _l Zone 8 7 = Bell 1 & 2 & Relay

3*71 Bell 1 & 2 Aux Relay Activation Zone 9 to 16

l__1 _l Zone 9 0 = None

l__1 _l Zone 10 1 = Bell 1

l__1 _l Zone 11 2 = Bell 2

l__1 _l Zone 12 3 = Bell 1 & 2

l__1 _l Zone 13 4 = Aux Relay

l__1 _l Zone 14 5 = Bell 1 & Relay

l__1 _l Zone 15 6 = Bell 2 & Relay

l__1 _l Zone 16 7 = Bell 1 & 2 & Relay

3*72 Bell 1 & 2 Aux Relay Activation Zone 17 to 24

l__1 _l Zone 17 0 = None

l__1 _l Zone 18 1 = Bell 1

l__1 _l Zone 19 2 = Bell 2

l__1 _l Zone 20 3 = Bell 1 & 2

l__1 _l Zone 21 4 = Aux Relay

l__1 _l Zone 22 5 = Bell 1 & Relay

l__1 _l Zone 23 6 = Bell 2 & Relay

l__1 _l Zone 24 7 = Bell 1 & 2 & Relay

3*73 Bell 1 & 2 Aux Relay Activation Zone 25 to 32

l__1 _l Zone 25 0 = None

l__1 _l Zone 26 1 = Bell 1

l__1 _l Zone 27 2 = Bell 2

l__1 _l Zone 28 3 = Bell 1 & 2

l__1 _l Zone 29 4 = Aux Relay

l__1 _l Zone 30 5 = Bell 1 & Relay

l__1 _l Zone 31 6 = Bell 2 & Relay

l__1 _l Zone 32 7 = Bell 1 & 2 & Relay

3*74 Bell 1 & 2 Aux Relay Activation Zone 33 to 40

l__1 _l Zone 33 0 = None

l__1 _l Zone 34 1 = Bell 1

l__1 _l Zone 35 2 = Bell 2

l__1 _l Zone 36 3 = Bell 1 & 2

l__1 _l Zone 37 4 = Aux Relay

l__1 _l Zone 38 5 = Bell 1 & Relay

l__1 _l Zone 39 6 = Bell 2 & Relay

l__1 _l Zone 40 7 = Bell 1 & 2 & Relay

3*75 Bell 1 & 2 Aux Relay Activation Zone 41 to 48

l__1 _l Zone 41 0 = None

l__1 _l Zone 42 1 = Bell 1

l__1 _l Zone 43 2 = Bell 2

l__1 _l Zone 44 3 = Bell 1 & 2

l__1 _l Zone 45 4 = Aux Relay

l__1 _l Zone 46 5 = Bell 1 & Relay

l__1 _l Zone 47 6 = Bell 2 & Relay

l__1 _l Zone 48 7 = Bell 1 & 2 & Relay

3*76 Bell 1 & 2 Aux Relay Activation Zone 49 to 56

l__1 _l Zone 49 0 = None

l__1 _l Zone 50 1 = Bell 1

l__1 _l Zone 51 2 = Bell 2

l__1 _l Zone 52 3 = Bell 1 & 2

l__1 _l Zone 53 4 = Aux Relay

l__1 _l Zone 54 5 = Bell 1 & Relay

l__1 _l Zone 55 6 = Bell 2 & Relay

l__1 _l Zone 56 7 = Bell 1 & 2 & Relay

3*77 Bell 1 & 2 Aux Relay Activation Zone 57 to 64

l__1 _l Zone 57 0 = None

l__1 _l Zone 58 1 = Bell 1

l__1 _l Zone 59 2 = Bell 2

l__1 _l Zone 60 3 = Bell 1 & 2

l__1 _l Zone 61 4 = Aux Relay

l__1 _l Zone 62 5 = Bell 1 & Relay

l__1 _l Zone 63 6 = Bell 2 & Relay

l__1 _l Zone 64 7 = Bell 1 & 2 & Relay

3*78 Bell 1 & 2 Aux Relay Activation Zone 70 to 72

l__0 _l Not Used 0 = None

l__0 _l Not Used 1 = Bell 1

l__0 _l Not Used 2 = Bell 2

l__0 _l Not Used 3 = Bell 1 & 2

l__0 _l Not Used 4 = Aux Relay

l__1 _l Zone 70 5 = Bell 1 & Relay

l__1 _l Zone 71 6 = Bell 2 & Relay

l__1 _l Zone 72 7 = Bell 1 & 2 & Relay

3*79 Bell 1 & 2 Aux Relay Activation Zone 73 to 75

l__1 _l Zone 73 0 = None

l__1 _l Zone 74 1 = Bell 1

l__1 _l Zone 75 2 = Bell 2

l__0 _l Not Used 3 = Bell 1 & 2

l__0 _l Not Used 4 = Aux Relay

l__0 _l Not Used 5 = Bell 1 & Relay

l__0 _l Not Used 6 = Bell 2 & Relay

l__0 _l Not Used 7 = Bell 1 & 2 & Relay

3*81 Bell 1 & 2 Aux Relay Activation Zone 95 to 99

l__0 _l Not Used 0 = None

l__0 _l Not Used 1 = Bell 1

l__0 _l Not Used 2 = Bell 2

l__0 _l Not Used 3 = Bell 1 & 2

l__0 _l Not Used 4 = Aux Relay

l__1 _l Zone 95 (1 & *) 5 = Bell 1 & Relay

l__0 _l Zone 96 (3 & #) 6 = Bell 2 & Relay

l__1 _l Zone 99 (* & #) 7 = Bell 1 & 2 & Relay

3*82 Enable Burg Features l__1 _l 0 = Disable

(Away, Stay, Max, Test, Instant, Chime Functions) 1 = Enable

3*85 Enable Fire & System Zone Bypass l__1 _l 0 = Disable

(For Zone Types 9, 16, 17 & 18 & Zones 70 to 77) 1 = Only Installer can Bypass

2 = Only Installer & Master can Bypass