Ademco Vista-32FB Program Sheet

This program sheet does not cover all the capabilities of this panel

Enter Program 1. 4140 or 5140 + 8 + 0 + 0 (Display should show 00)

or

2. Power down then back up and press * and # within 1 minute

Move to Location * + Location

View Location # + Location (Display will read off one digit at a time)

Exit Program 1. *98 exits and does not allow re-entry to programming without cycling power and pressing * and #

or

2. *99 exits and does allow re-entry by Installer Code + 8 + 00

Programming can be re-entered up to 1 minute after exiting with * and # (# + 0 disables this feature)

Default Panel *97

Compatibility

Power Ratings 1A Aux output standby 1.7A Aux output in alarm

  1. 7A each Siren output

Device Address All keypads, receivers and expanders must be addressed and added in #93 menu

Address 00 and 01 are pre-programmed as alpha keypads

Address first keypad as 00 to allow entry into programming

00 Alpha Keypad (cannot be changed)

  1. to 30 Keypads, zone expanders, wireless receivers etc

Keypad Address (6128/6139/6150/6160 keypads)

  1. Remove power from keypad then power back up

  2. Hold 1 & 3 for 3 seconds, "ADDR = XX" or "XX" should appear (XX = current address)

  3. Within 10 seconds enter 00 to erase old address then enter new address (00 to 30)

  4. Press * to save and exit

(6128RF/6150RF keypads)

  1. Power keypad down then back up or remove backplate

  2. Within 30 seconds hold 1 & 3 for 3 seconds until flashing " - - 0 0"

  3. Press 1 and "cA XX" should appear (XX = current address)

  4. Enter new address (00 to 30) then * to exit back to flashing " -- 0 0"

  5. Press * to exit

Sniffer Test (Tests wireless sensors)

  1. Installer Code + # + 3

  2. Keypad displays all wireless sensors, faulting sensor removes it from list

  3. Exit with Installer Code + 1 (OFF)

Go-No Go Test (Verifies adequate RF by reducing receiver signal strength by 50%)

  1. Installer Code + # + 4

  2. a. Siren sounds

b. Panel may send walk test signal (If test signal was programmed)

c. "dd" appears on screen

d. Keypad will beep every 15 seconds

  1. Fault sensor, keypad should beep 3 times and display zone number,

if no beeps sound reorient or move sensor a few inches and try again

  1. Exit with Installer Code + 1 (OFF)

Default Panel * + 97, answer YES if using alpha keypads

All Zone programming is done by # 93 menu, enter #93 for below menu (Click to go to section)

Tech_201000000129.gif 1 enters, 0 moves to next menu (Squential Learning)

Tech_201000000223.gif 1 enters, 0 moves to next menu (Report Codes)

Tech_201000000224.gif 1 enters, 0 moves to next menu (Alpha Zone Programming)

Tech_201000000130.gif 1 enters, 0 moves to next menu (Device Programming)

Tech_201000000131.gif 1 enters, 0 moves to next menu (Relay Programming)

Tech_201000000225.gif 1 enters, 0 moves to next menu (Relay/Voice Descriptors)

Tech_201000000226.gif 1 enters, 0 moves to next menu (Custom Index)

Tech_201000000227.gif 1 enters, 0 moves to next menu (Clear RF Serial #'s)

Tech_201000000228.gif 1 enters, 0 moves to next screen

Tech_201000000132.gif 1 exits #93 menu, 0 moves back to Zone Program

  1. = Enable

  1. = Partition 1

  2. = Partition 2

9 = Silence Bell if Fire Present

  1. = Enable

  1. = Enable

  1. = Randomize 10 - 40 minutes

  2. = Randomize 6 - 12 Hours

  1. nd Digit = 11 for * 12 for #

(Partition Specific) I _1 _I 996 3 & # 1 = Enable

I _1 _I 999 * & #

  1. = Enable

  1. = Ignore Zone Tampers

  1. = Enable

  1. = No Test report if any other report was recently sent

  1. to 199 Hours

  1. = Yes

(Partition Specific) 1 = # + 2 = Away Arm

# + 3 = Stay Arm

# + 4 = Maximum Arm

# + 7 = Instant Arm

  1. = Touch-Tone

(Example 9 is 09* )

(Example 1234 is 01 02 03 04) Hex B = 11 C = 12 D = 13 E = 14 F = 15

(17 digits, end with * ) # + 11 = * # + 12 = # # + 13 = 2.5 second pause

(15's Default CSID to Factory)

l__1 _l System Shutdown 1 = Enable

l__0 _l Not Used

l__1 _l Remote Bypass

l__1 _l Remote Disarm

l__1 _l Remote Arm

l__1 _l Upload Programming

l__1 _l Download Programming

  1. to 032 = Zone 01 to 32 cannot be bypassed

  1. = Enable

  1. = Enable

  1. = Zones 3 to 8 Normally Closed Loops

  1. = 11 seconds

  2. = 30 seconds

  1. = Wait for True Dial Tone

  1. to 14 = Rings to Answer

15 = Answering Machine Over-Ride

  1. = Contact ID

  2. = Ademco High Speed

  3. = Ademco Express

  1. = Sescoa/Radionics

  1. = Contact ID

  2. = Ademco High Speed

  3. = Ademco Express

  1. = Sescoa/Radionics

  1. = Enable

  1. = Sescoa

  1. = Reports sent to Primary and Secondary Numbers

for Primary I _0 _I Restore 1 = Expanded

I _0 _I Bypass

I _0 _I Trouble

I _0 _I Open/Close

I _0 _I Low Bat/Walk Test

for Secondary I _0 _I Restore 1 = Expanded

I _0 _I Bypass

I _0 _I Trouble

I _0 _I Open/Close

I _0 _I Low Bat/Walk Test

  1. = Enable

  1. = Enable

I _0 _I Trouble 1 = Expanded

I _0 _I Bypass

I _0 _I Open/Close

I _0 _I System

I _0 _I Test

I _0 _I Trouble 1 = Expanded

I _0 _I Bypass

I _0 _I Open/Close

I _0 _I System

I _0 _I Test

  1. = Enable

End Phone with * # + 11 = *, # + 12 = #, # + 13 = 2.5 second pause

End with *

I _0 _I Zone Type 1 0 = No Restoral Report

I _0 _I Zone Type 2 1 = Restoral Report

I _0 _I Zone Type 3

I _0 _I Zone Type 4

I _0 _I Zone Type 5

I _0 _I Zone Type 6

I _0 _I Zone Type 7

I _0 _I Zone Type 8

I _1 _I _2 _I Hours 00 to 23

I _0 _I _0 _I Minutes 00 to 59

  1. to 15 = 01 to 15 Alarms

(Partition Specific) I _1 _I Zone 996 (3 & #) 1 = Enable

I _1 _I Zone 999 (* & #)

I _1 _I Zone 992 (Duress)

(Partition Specific) 1 = Continuous during Entry Delay

  1. = 16 seconds

  1. = At Bell Timeout

  2. = At Disarm

Hex B = 11, C = 12, D = 13, E = 14, F = 15

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

To access 2nd Level of Programming press *94 then enter * + 2-digits, to exit back to 1st Level Programming enter *99

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

  1. *17 Common Lobby Partition l__0 _l 0 = Disable

  1. = Partition 1

  2. = Partition 2

  1. *18 Affects Lobby l__0 _l 0 = Does Not Affect Lobby

  1. = Affects Lobby

  1. *19 Arms Lobby l__0 _l 0 = Does Not Arm Lobby

  1. = Arms Lobby

  1. *20 Exit Error Logic l__0 _l 0 = Disable

  1. = Bypass E/E & Interior Zones

faulted after Exit Delay

  1. *21 Exit Delay Reset l__0 _l 0 = Disable

  1. = Resets Exit Delay to 60 seconds after Zone is Closed

  1. *22 Cross-Zoning Pair One I _0 _I _0 _I _0 _I I _0 _I _0 _I _0 _I Enter 2 separate zones

  1. *23 Cross-Zoning Pair Two I _0 _I _0 _I _0 _I I _0 _I _0 _I _0 _I Both must fault within 5 minutes to sound alarm

  1. *24 Cross-Zoning Pair Three I _0 _I _0 _I _0 _I I _0 _I _0 _I _0 _I

  1. *25 Cross-Zoning Pair Four I _0 _I _0 _I _0 _I I _0 _I _0 _I _0 _I

  1. *26 Panic Button or Speedkey Macro I _0 _I _0 _I A Key 1 &* 00 = Panic Button

(Function Keys) I _0 _I _0 _I B Key 3 & # 01 to 35 = Macro

I _0 _I _0 _I C Key * & #

I _0 _I _0 _I D Key

  1. *28 RF TX Low Battery Sound l__0 _l 0 = When Disarmed

  1. = Immediate

  1. *29 RF TX Low Battery Report Enable l__0 _l 0 = Disable

  1. = Enable

  1. *30 RF RCVR Check-In Interval l__0 _l__2 _l 02 to 15 x2 Hours

  1. *31 RF Transmitter Check-In Interval l__0 _l__2 _l 02 to 15 x2 Hours

  1. *33 Touch Tone with Rotary Backup l__1 _l 0 = Disable

  1. = Enable

  1. *34 Communication Split Report Selection I _0 _I 0 = Disable

  1. = Alarm reports to Primary, others Secondary

  2. = O/C and Test reports to Secondary, others Primary

  1. *42 Call Waiting Defeat I _0 _I 0 = Disable

  1. = Enable

  1. *43 Permanent Keypad Backlight I _1 _I 0 = Disable

  1. = Enable

  1. *44 Wireless Keypad Tamper Detect I _0 _I 0 = Disable

  1. = Enable

  1. *45 Exit Delay Sounder I _0 _I 1 = Enable

0 = Disable

  1. *47 Chime on Bell Output 1 I _0 _I 0 = Disable

  1. = Enable

  1. *48 Wireless Keypad Assignment I _0 _I 0 = Disable

  1. = Partition 1

  2. = Partition 2

  1. *49 Suppress TX Supervision Sound I _1 _I 0 = Enable

  1. = Disable

  1. *52 Send Cancel if Alarm + Off I _0 _I 0 = No Restriction

  1. = Within Bell Timeout

  1. *53 Download Callback I _1 _I 0 = Callback Required

  1. = No Callback

  1. *56 50/60 Hz Clock Speed I _0 _I 0 = 60 Hz

  1. = 50 Hz

  1. *57 Enable 5800RF Global Arm I _0 _I 0 = Disable

  1. = Enable

  1. *58 Enable 5800RF Force Arm I _0 _I 0 = Disable

  1. = Enable

  1. *60 Zone 5 Audio Alarm Verification I _0 _I 0 = Disable

  1. = Enable

  1. *70 Event Log Types I _1 _I Alarm 0 = Disable Logging

I _1 _I Check 1 = Enable Logging

I _1 _I Bypass

I _1 _I O/C

I _1 _I System

I _1 _I Test

  1. *71 12/24 Hour Time Stamp Format I _0 _I 0 = 12 Hour

  1. = 24 Hour (Military)

  1. *72 Event Log Printer On-line Mode I _0 _I 0 = Disable

  1. = Enable

  1. *73 Printer Baud Rate I _0 _I 0 = 1200 Baud

  1. = 300 Baud

  1. *74 Relay Timeout Minutes I _0 _I _0 _I _0 _I 0 to 127 x2 minutes

  1. *75 Relay Timeout Seconds I _0 _I _0 _I _0 _I 0 to 127 seconds

  1. *76 Access Control Relay for Partition I _0 _I _0 _I 00 = None

(Partition Specific) 01 to 08 = Relay used when Code + 0

  1. *77 Log First Maintenance Signal I _0 _I 0 = No Log

1 = Log each maintenance Signal from each smoke

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

To access 3rd Level of Programming press *94 then enter * + 2-digits, to exit back to 2nd Level Programming enter *99

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

  1. *00 Number of Partitions I _1 _I 1 or 2 = Partition 1 or 2

2*01 Daylight Savings Time I _0 _I _4 _I Start 00 = Disable 07 = July

Start/End Month I _1 _I _0 _I End 01 = January 08 = August

02 = February 09 = September

  1. = March #10 = October

  2. = April #11 = November

  3. = May #12 = December

  4. = June

2*02 Daylight Savings Time I _1 _I Start 1 = 1st Weekend

Start/End Weekend I _5 _I End 2 = 2nd Weekend

3 = 3rd Weekend

4 = 4th Weekend

5 = Last Weekend

6 = Next to Last Weekend

  1. = 3rd from Last Weekend

2*05 Auto-Arm Delay I _1 _I _5 _I 00 = Instant

(Partition Specific) 15 = Auto-Arm Disabled

  1. to 14 x4 Minutes

  2. *06 Auto-Arm Warning Period I _0 _I _0 _I 00 = Instant at end of Arming Delay

(Partition Specific) 01 to 15 Minutes

2*07 Auto-Disarm Delay I _1 _I _5 _I 00 = Instant at end of Window

(Partition Specific) 01 to 14 x4 Minutes

15 = No Auto-Disarm

2*08 Enable Force Arm for Auto-Arm I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

2*09 Open/Close Reports by Exception I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

2*10 Allow Disarm only during I _1 _I 0 = Disable

Arm/Disarm Window 1 = Enable

(Partition Specific)

2*11 Allow Disarm Outside Window I _1 _I 0 = Disable

If Alarm Occurs 1 = Enable

(Partition Specific)

2*18 Enable Goto For This Partition I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

2*19 Use Partition Descriptors I _1 _I 0 = Disable

  1. = Display Partition Number and 4-digit Descriptor

  2. *20 Enable J7 Triggers by Partition I _1 _I 0 = Disable for displayed Partition

(Partition Specific) 1 = Enable for displayed Partition

2*21 Enable Supervision Pulses for I _0 _I Fire 0 = Disable

Long Range Radio Trigger Outputs I _0 _I Burglary 1 = Enable

I _0 _I Silent Panic/

Duress

2*22 Display Fire Alarms of Other Partitions I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

2*23 Display Burg/Panics of Other Partitions I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

2*24 Display Troubles of Other Partitions I _1 _I 0 = Disable

(Partition Specific) 1 = Enable

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

To access 4th Level of Programming press *94 then enter * + 2-digits, to exit back to 3rd Level Programming enter *99

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------

  1. *00 Display Trouble instead of Check I _0 _I 0 = Check Displayed

  1. = Trouble Displayed

3*01 Fire Display Lock I _0 _I 0 = Scroll All Alarms

  1. = Lock Display of first Fire Alarm

3*12 Zone Type 18 Delay Use I _1 _I 0 = Check Displayed

  1. = Trouble Displayed

3*13 Supv N.O./N.C. Selection I _0 _I 0 = Supervision on Short/Trouble on Open

  1. = Supervision on Short or Open

3*15 Alarm Bell Sound I _1 _I Bell 1 0 = Pulsed

I _0 _I Bell 2 1 = Steady

3*16 Delay for Zone Types 17 & 18 I _0 _I _0 _I 00 to 15 x2 seconds

(Waterflow & Fire Supervision)

3*17 Alt Function (Tamper) for Zone 6 I _0 _I _0 _I 0 = Disable

  1. = Enable

3*18 Extended Delay for Types 17 & 18 I _0 _I 0 = No

  1. = Yes

3*19 Enable J2 Header Printer Port I _0 _I 0 = Pins 5 & 9 function per 3*20

  1. = Pins 5 & 9 as printer RXD & DTR

3*20 Trigger Outputs Selection I _0 _I 0 = Lorra Full Connection

  1. = Lorra Limited Connection/Keyswitch

  2. = Lorra Fire Connection & 5140LED

  3. *21 Max # of Dialer Retries I _8 _I 1 to 8 attempts

3*30 Dialer Selection I _1 _I Main 0 = Disable

I _0 _I Backup 1 = Enable

3*31 Backup Dialer Touch-Tone/Rotary I _0 _I 0 = Rotary

  1. = Touch-Tone

3*50 Zone Type Restore Enable I _1 _I Zone Type 16 0 = Disable

For Zone Types 16 to 18 I _1 _I Zone Type 17 1 = Enable

I _1 _I Zone Type 18

3*55 Reset on second OFF for Bell 1 I _0 _I 0 = Disable

  1. = Enable

3*56 Reset on second OFF for Bell 2 I _0 _I 0 = Rotary

  1. = Touch Tone

3*57 Bell 2/Aux Relay Confirm Am Ding I _0 _I Bell 2 0 = Disable

I _0 _I Aux 1 = Enable

3*59 Bell 2/Aux Relay Chime Annunciation I _0 _I Bell 2 0 = Disable

I _0 _I Aux 1 = Enable

3*60 Bell 2/Aux Relay Timeout I _0 _I _0 _I Bell 2 00 = No Timeout

I _0 _I _0 _I Aux Relay 01 to 15 x2 Minutes

3*61 Aux Relay Function I _1 _I Bell 2 0 = Trouble/Supervisory

  1. = Alarm/Silenced by Code + OFF

  2. = Smoke Detector Reset

  3. = Battery Save

  4. = Alarm, Silenced by Code + # + 67

3*82 Enable Burg Features I _1 _I 0 = Disable

(Away, Stay, Max, Test, Instant, Chime Functions) 1 = Enable

3*85 Enable Fire & System Zone Bypass I _1 _I 0 = Disable

Zone Types 9, 16, 17, 18, Zones 70 to 77 1 = Only Installer Code can Bypass

(Partition 1 only) 2 = Only Installer and Master Code can Bypass