Fire-Lite 411 Communicator

This is a 3-channel dialer that connects to a fire panel that has no communicator

The 411 can only be programmed by a PRO-411 DACT Programmer, the 411UD can be downloaded

Enter Program 1. Press MODE (Display goes blank)

2. Within 10 seconds enter 7764 (Display will show numbers entered)

3. Press ENTER/STORE key (Display shows "00_ ", Trouble LED blinks)

("00_ " Is 1st location in programming and data in that location)

Program Keys Tech_201000002553.gif = Selects Operating Mode

Tech_201000002551.gif = Go to next Address (Location)

Tech_201000002552.gif = Go to previous Address

Tech_201000002550.gif = Press once to go to Address 00

Tech_201000002550.gif = Press twice then enter Address to go to then Tech_201000002554.gif

Tech_201000002554.gif = Saves Data and goes to next Address

Enter Data Enter data in each location (0 to F) + ENTER/STORE to save and move to next location

Exit Program MODE + 6676 + ENTER/STORE (Returns to Normal Mode)

Initiate Download MODE + 3696 + ENTER/STORE

Primary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _I _I

Location 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Primary Format I A _I 0 = 4 + 1 Ademco Express Standard DTMF, 1400/2300 Ack

Location 20 1 = 4 + 2 Ademco Express Standard DTMF, 1400/2300 Ack

2 = 3 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

3 = 3 + 1 Expanded 1800 Hz Carrier 2300 Hz Ack

4 = 3 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

5 = 3 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

6 = 4 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

7 = 4 + 1 Expanded 1800 Hz Carrier, 2300 Hz Ack

8 = 4 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

9 = 4 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

A = 4 + 2 Standard 1800 Hz Carrier, 2300 Hz Ack

B = 4 + 2 Expanded 1800 Hz Carrier, 2300 Hz Ack

C = 4 + 2 Standard 1900 Hz Carrier, 1400 Hz Ack

D = 4 + 2 Expanded 1900 Hz Carrier, 1400 Hz Ack

E = Contact ID, 1400/2300 Ack

F = Not Used

Primary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 21 22 23 24

Primary 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 25 26 27 28

Primary Test Interval I 0 _I 0 = 24 Hours

Location 29 1 = 12 Hours

2 = 8 Hours

3 = 6 Hours

Secondary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _I _I

Location 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Secondary Format I A _I

Location 50

Secondary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 51 52 53 54

Sec. 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 55 56 57 58

Sec. Test Interval I 0 _I 0 = 24 Hours

Location 59 1 = 12 Hours

2 = 8 Hours

3 = 6 Hours

AC Loss Report Delay I 0 _I 0 = 6 Hours 8 = 16 Hours

Location 60 1 = 7 Hours 9 = 17 Hours

2 = 8 Hours A = 18 Hours

3 = 9 Hours B = 19 Hours

4 = 10 Hours C = 20 Hours

5 = 11 Hours D = 21 Hours

6 = 12 Hours E = 22 Hours

7 = 15 Hours F = 23 Hours

Backup Reporting I 0 _I 0 = Report to Secondary Phone if Primary Fails

Location 61 1 = Report to Both Primary and Secondary

2 = 1st Available Receiver

Not Used I _I

Location 62

DACT Trble Reminder I 0 _I 0 = Disabled

Location 63 1 = Reminder Beep every 2 minutes on Trouble

Communicator Enable I 1 _I 0 = Communicator Disabled

Location 64 1 = Communicator Enabled

Input Channel 1 Function Selection

I 0 _I 0 = Activation on Fire Alarms (2-wire Smoke)

Location 65 1 = Pull Station

2 = Normally Open Contact Device

Input Channel 2 Function Selection 3 = Host Panel Trouble

I 1 _I 4 = Fire Supervisory

Location 66 5 = Fire Supervisory Resettable

6 = Waterflow Silenceable

Input Channel 3 Function Selection 7 = Waterflow Non-Silenceable

I 2 _I 8 = Process Monitoring

Location 67 9 = Process Monitoring Auto-Resettable

Reserved for Future Use

I 0 _I

68

Input Channel 1 Delay Timer

I 0 _I 0 _I 0 _I 000 to 179 Seconds

Location 69 70 71

Input Channel 2 Delay Timer

I 0 _I 0 _I 0 _I 000 to 179 Seconds

Location 72 73 74

Input Channel 3 Delay Timer

I 0 _I 0 _I 0 _I 000 to 179 Seconds

Location 75 76 77

Reserved for Future I 0 _I 0 _I 0 _I

Location 78 79 80

Touchtone Select for Primary Phone

I 0 _I 0 = TouchTone Dialing

Location 81 1 = Pulse Dialing

Make/Break Ration for Primary Phone

I 0 _I 0 = 67/33 Ratio

Location 82 1 = 62/38 Ratio

Touchtone Select for Secondary Phone

I 0 _I 0 = TouchTone Dialing

Location 83 1 = Pulse Dialing

Make/Break Ration for Secondary Phone

I 0 _I 0 = 67/33 Ratio

Location 84 1 = 62/38 Ratio

Reserved for Future I 0 _I

Location 85

Reserved for Future I 0 _I

Location 86

Reserved for Future I 0 _I

Location 87

Reserved for Future I 0 _I

Location 88

Trouble Call Limit I 0 _I 0 = Call for each Trouble and Alarm

Location 89 1 = 10 Calls before shutdown

Everything from 90 to 137 Reserved

4/2 Standard and 4/2 Express Report Codes

Address Description 4/2 Reporting

138 - 139 Primary # Input Channel 1 Active Event Code 11

140 - 141 Primary # Input Channel 2 Active Event Code FF

142 - 143 Primary # Input Channel 3 Active Event Code 83

144 - 145 not used

146 - 147 Primary # Input Channel 1 Fault Event Code F1

148 - 149 Primary # Input Channel 2 Fault Event Code F2

150 - 151 Primary # Input Channel 3 Fault Event Code F3

152 - 153 not used

154 - 155 Primary # Phone Line 1 Voltage Fault Event Code 64

156 - 157 Primary # Phone Line 2 Voltage Fault Event Code 65

158 - 159 Primary # Phone Number 1 Comm. Fault Event Code 6A

160 - 161 Primary # Phone Number 2 Comm. Fault Event Code 6B

162 - 163 Primary # System Off Normal Fault Code 6F

164 - 165 Primary # Input Channel 1 Active Restoral Code E1

166 - 167 Primary # Input Channel 2 Active Restoral Code E2

168 - 169 Primary # Input Channel 3 Active Restoral Code E3

170 - 171 not used

172 - 173 Primary # Input Channel 1 Fault Restoral Code D1

174 - 175 Primary # Input Channel 2 Fault Restoral Code D2

176 - 177 Primary # Input Channel 3 Fault Restoral Code D3

178 - 179 not used

180 - 181 Primary # Phone Line 1 Restoral Code A4

182 - 183 Primary # Phone Line 2 Restoral Code A5

184 - 185 Primary # Phon Number 1 Restoral Code AA

186 - 187 Primary # Phon Number 2 Restoral Code AB

188 - 189 Primary # System Off Normal Restoral Code AF

190 - 191 Primary # System Test Message 99

192 - 193 Primary # System Abnormal Test Message 91

194 - 195 not used

196 - 197 not used

198 - 199 not used

200 - 201 not used

202 - 203 Secondary # Input Channel 1 Active Event Code 11

204 - 205 Secondary # Input Channel 2 Active Event Code FF

206 - 207 Secondary # Input Channel 3 Active Event Code 83

208 - 209 not used

210 - 211 Secondary # Input Channel 1 Fault Event Code F1

212 - 213 Secondary # Input Channel 2 Fault Event Code F2

214 - 215 Secondary # Input Channel 3 Fault Event Code F3

216 - 217 not used

218 - 219 Secondary # Phone Line 1 Voltage Fault Event Code 64

220 - 221 Secondary # Phone Line 2 Voltage Fault Event Code 65

222 - 223 Secondary # Phone Number 1 Comm. Fault Event Code 6A

224 - 225 Secondary # Phone Number 2 Comm. Fault Event Code 6B

226 - 227 Secondary # System Off Normal Fault Code 6F

228 - 229 Secondary # Input Channel 1 Active Restoral Code E1

230 - 231 Secondary # Input Channel 2 Active Restoral Code E2

232 - 233 Secondary # Input Channel 3 Active Restoral Code E3

234 - 235 not used

236 - 237 Secondary # Input Channel 1 Fault Restoral Code D1

238 - 239 Secondary # Input Channel 2 Fault Restoral Code D2

240 - 241 Secondary # Input Channel 3 Fault Restoral Code D3

242 - 243 not used

244 - 245 Secondary # Phone Line 1 Restoral Code A4

246 - 247 Secondary # Phone Line 2 Restoral Code A5

248 - 249 Secondary # Phone Number 1 Restoral Code AA

250 - 251 Secondary # Phone Number 2 Restoral Code AB

252 - 253 Secondary # System Off Normal Restoral Code AF

254 - 255 Secondary # System Test Message 99

256 - 257 Secondary # System Abnormal Test Message 91

258 - 259 not used

260 - 261 not used

262 - 263 not used

264 - 265 not used