Fire-Lite MS-5024UD/5024UDE Program Sheet (Under Construction)

Enter Program 1. Press MODE (Display goes blank)

2. Within 10 seconds enter 7764 (Display will show numbers entered)

3. Press ENTER/STORE key (Display shows "00_ ", Trouble LED blinks)

("00_ " Is 1st location in programming and data in that location)

Program Keys Tech_201000002553.gif = Selects Operating Mode

Tech_201000002551.gif = Go to next Address (Location)

Tech_201000002552.gif = Go to previous Address

Tech_201000002550.gif = Press once to go to Address 00

Tech_201000002550.gif = Press twice then enter Address to go to then Tech_201000002554.gif

Tech_201000002554.gif = Saves Data and goes to next Address

Enter Data Enter data in each location (0 to F) + ENTER/STORE to save and move to next location

Exit Program MODE + 6676 + ENTER/STORE (Returns to Normal Mode)

Initiate Download MODE + 3696 + ENTER/STORE

Primary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Primary Format I A _I 0 = 4 + 1 Ademco Express Standard DTMF, 1400/2300 Ack

Location 16 1 = 4 + 2 Ademco Express Standard DTMF, 1400/2300 Ack

2 = 3 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

3 = 3 + 1 Expanded 1800 Hz Carrier 2300 Hz Ack

4 = 3 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

  1. = 3 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

  2. = 4 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

  3. = 4 + 1 Expanded 1800 Hz Carrier, 2300 Hz Ack

  4. = 4 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

  5. = 4 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

A = 4 + 2 Standard 1800 Hz Carrier, 2300 Hz Ack

B = 4 + 2 Expanded 1800 Hz Carrier, 2300 Hz Ack

C = 4 + 2 Standard 1900 Hz Carrier, 1400 Hz Ack

D = 4 + 2 Expanded 1900 Hz Carrier, 1400 Hz Ack

E = Not Used

F = Not Used

Primary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 17 18 19 20

Primary 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 21 22 23 24

Primary Test Interval I 0 _I 0 = 24 Hours 2 = 8 Hours

Location 25 1 = 12 Hours 3 = 6 Hours

Secondary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Secondary Format I A _I

Location 42

Secondary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 43 44 45 46

Sec. 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 47 48 49 50

Sec. Test Interval I 0 _I 0 = 24 Hours 2 = 8 Hours

Location 51 1 = 12 Hours 3 = 6 Hours

Alarm Verification I 0 _I 0 = No Verification

Location 52 1 = Verification (only for 2-wire Smokes)

Future Use I _ _I _ _I _ _I

Location 53 54 55

Slave Com,/Fire Panel I 2 _I 0 = Fire Panel only

Location 56 1 = Slave Communicator Only

2 = Fire Panel/Communicator

Zone 1 - 5 Function I 0 _I 0 _I 0 _I 0 _I 0 _I 0 = Operates 2-Wire Smoke Detector

Location 57 58 59 60 61 1 = Pull Station

Zone 1 2 3 4 5 2 = Normally Open Contact Device

3 = Supervisory

4 = Supervisory, Auto Resettable, Self

Restore function, not latched

5 = Waterflow, Silenceable, Silence of Silenceable

Notification Circuits Allowed, Affects Zone 3

Only

6 = Waterflow, non - silenceable, Silence of

Silenceable Notification Circuits Allowed,

Affects Zone 3 Only

Waterflow Retard Timer I 0 _I 0 _I 00 to 89 seconds

Location 62 63

AC Loss Report Delay I 0 _I 0 = 6 Hours 8 = 16 Hours

Location 64 1 = 7 Hours 9 = 17 Hours

2 = 8 Hours A = 18 Hours

3 = 9 Hours B = 19 Hours

4 = 10 Hours C = 20 Hours

5 = 11 Hours D = 21 Hours

6 = 12 Hours E = 22 Hours

7 = 15 Hours F = 23 Hours

Alarm Presignal I 0 _I 0 = No Presignal

Location 65 1 = Delay before transmission

Presignal Delay Timer I 1 _I 2 _I 0 _I 000 to 179 minutes

Location 66 67 68

Notification Appliance Circuit 1 Enable 0 = Silenceable

I 0 _I 1 = Non-Silenceable

Location 69 2 = Disabled

(2 causes "bEL2" to display & sounds piezo)

Silence inhibit Notification Circuit 1 0 = No silence inhibit

I 0 _I 1 = Prohibits silencing for 1 minute

Location 70

Auto Silence notification Notification Circuit 1 0 = No autosilence 4 = 20 minutes

I 0 _I 1 = 5 minute autosilence 5 = 25 minutes

Location 71 2 = 10 minutes 6 = 30 minutes

3 = 15 minutes

Coding, Notification Appliance Circuit 1 0 = Steady

I 0 _I 1 = March Time (120ppm)

Location 72 2 = California (10 sec ON, 5 sec OFF)

3 = Temporal (.5 sec ON, .5 sec OFF)

Notification Appliance Circuit 2 Enable 0 = Silenceable

I 0 _I 1 = Non-Silenceable

Location 73 2 = Disabled

(2 causes "bEL2" to display & sounds piezo)

Silence inhibit Notification Circuit 2 0 = No silence inhibit

I 0 _I 1 = Prohibits silencing for 1 minute

Location 74

Auto Silence notification Notification Circuit 2 0 = No autosilence 4 = 20 minutes

I 0 _I 1 = 5 minute autosilence 5 = 25 minutes

Location 75 2 = 10 minutes 6 = 30 minutes

3 = 15 minutes

Coding, Notification Appliance Circuit 2 0 = Steady

I 0 _I 1 = March Time (120ppm)

Location 76 2 = California (10 sec ON, 5 sec OFF)

3 = Temporal (.5 sec ON, .5 sec OFF)

Trouble Reminder I 0 _I 0 = Disabled

Location 77 1 = Trouble Reminder beep every 15 sec

after alarm, beep every 2 minutes

Annunciator/Printer Supervision 0 = No Annunciator or Printer

I 0 _I 1 = Annunciator present

Location 78 2 = Printer present

3 = Annunciator and Printer present

Backup Reporting I 0 _I 0 = Secondary Phone as Backup

Location 79 1 = All reports to Secondary Phone

TouchTone/Rotary I 0 _I 0 = TouchTone Dialing both Numbers

Location 80 1 = Rotary Dialing both Numbers

Make Break Ratio I 0 _I 0 = Make/Break Ratio 67/33

Location 81 1 = Make/Break Ratio 62/38

Future Use I 0 _I

Location 82

Future Use I 0 _I

Location 83

Panel ID Number I _I _I _I _I

Location 84 85 86 87

Service Terminal 1 Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Ring Count on Primary Phone Line

I 1 _I 0 _I 00 = Disabled, 01 to 25 Rings

Location 104 105

Fax/Answer Machine Primary Phone Line

I 0 _I 0 = No Sharing of Primary Line with Fax

Location 106 1 = Wait for 3 calls 30 seconds apart

Service Terminal 2 Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Ring Count on Secondary Phone Line

I 1 _I 0 _I 00 = Disabled, 01 to 25 Rings

Location 123 124

Fax/Answer Machine Secondary Phone Line

I 0 _I 0 = No Sharing of Primary Line with Fax

Location 125 1 = Wait for 3 calls 30 seconds apart

Upload/Download Reports sent to Secondary Phone

I 0 _I 0 = Backup Only

Location 126 1 = Always

Report Codes (Leave at default!)

Address Description Settings

127 - 128 Primary # Zone 1 Alarm Code 11

129 - 130 Primary # Zone 2 Alarm Code 12

131 - 132 Primary # Zone 3 Alarm Code 13

133 - 134 Primary # Zone 4 Alarm Code 14

135 - 136 Primary # Zone 5 Alarm Code 15

137 - 138 Primary # Zone 1 Disable Code F1

139 - 140 Primary # Zone 2 Disable Code F2

141 - 142 Primary # Zone 3 Disable Code F3

143 - 144 Primary # Zone 4 Disable Code F4

145 - 146 Primary # Zone 5 Disable Code F5

147 - 148 Primary # Drill Code 97

149 - 150 Primary # AC Fault Code F6

151 - 152 Primary # Zone 1 Fault Code F1

153 - 154 Primary # Zone 2 Fault Code F2

155 - 156 Primary # Zone 3 Fault Code F3

157 - 158 Primary # Zone 4 Fault Code F4

159 - 160 Primary # Zone 5 Fault Code F5

161 - 162 Primary # Earth Fault Code F7

163 - 164 Primary # Low Battery Fault Code F8

165 - 166 Primary # No Battery Fault Code F9

167 - 168 Primary # Telco Pri. Line Fault Code FA

169 - 170 Primary # Telco Sec. Line Fault Code FB

171 - 172 Primary # NAC #1 Fault Code FC

173 - 174 Primary # NAC #2 Fault Code FC

175 - 176 Primary # Comm Trouble Pri. # Code FD

177 - 178 Primary # Comm Trouble Sec. # Code FE

179 - 180 Primary # Annunciator Fault Code FC

181 - 182 Primary # System Off Normal Code FF

183 - 184 Primary # Zone 1 Alarm Restore Code E1

185 - 186 Primary # Zone 2 Alarm Restore Code E2

187 - 188 Primary # Zone 3 Alarm Restore Code E3

189 - 190 Primary # Zone 4 Alarm Restore Code E4

191 - 192 Primary # Zone 5 Alarm Restore Code E5

193 - 194 Primary # Zone 1 Disable Restore Code E1

195 - 196 Primary # Zone 2 Disable Restore Code E2

197 - 198 Primary # Zone 3 Disable Restore Code E3

199 - 200 Primary # Zone 4 Disable Restore Code E4

201 - 202 Primary # Zone 5 Disable Restore Code E5

203 - 204 Primary # Drill Restore Code 98

205 - 206 Primary # AC Fault Restore Code E6

207 - 208 Primary # Zone 1 Fault Restore Code E1

209 - 210 Primary # Zone 2 Fault Restore Code E2

211 - 212 Primary # Zone 3 Fault Restore Code E3

213 - 214 Primary # Zone 4 Fault Restore Code E4

215 - 216 Primary # Zone 5 Fault Restore Code E5

217 - 218 Primary # Earth Fault Restore Code E7

219 - 220 Primary # Low Battery Fault Restore Code E8

221 - 222 Primary # No Battery Fault Restore Code E9

223 - 224 Primary # Telco Pri. Line Fault Restore Code EA

225 - 226 Primary # Telco Sec. Line Fault Restore Code EB

227 - 228 Primary # NAC #1 Fault Restore Code EC

229 - 230 Primary # NAC #2 Fault Restore Code EC

231 - 232 Primary # Comm Trouble Pri. # Restore Code ED

233 - 234 Primary # Comm Trouble Sec. # Restore Code EE

235 - 236 Primary # Annunciator Fault Restore Code EC

237 - 238 Primary # System Off Normal Restore Code EF

239 - 240 Primary # System Test Report 99

241 - 242 Primary # System Abnormal Test Report 91

243 - 244 Primary # Request for Up/Download 71

245 - 246 Primary # Successful Upload 72

247 - 248 Primary # Successful Download 73

249 - 250 Primary # Failed Up/Download 74

Address Description Setting

251 - 252 Secondary # Zone 1 Alarm Code 11

253 - 254 Secondary # Zone 2 Alarm Code 12

255 - 256 Secondary # Zone 3 Alarm Code 13

257 - 258 Secondary # Zone 4 Alarm Code 14

259 - 260 Secondary # Zone 5 Alarm Code 15

261 - 262 Secondary # Zone 1 Disable Code F1

263 - 264 Secondary # Zone 2 Disable Code F2

265 - 266 Secondary # Zone 3 Disable Code F3

267 - 268 Secondary # Zone 4 Disable Code F4

269 - 270 Secondary # Zone 5 Disable Code F5

271 - 272 Secondary # Drill Code 97

273 - 274 Secondary # AC Fault Code F6

275 - 276 Secondary # Zone 1 Fault Code F1

277 - 278 Secondary # Zone 2 Fault Code F2

279 - 280 Secondary # Zone 3 Fault Code F3

281 - 282 Secondary # Zone 4 Fault Code F4

283 - 284 Secondary # Zone 5 Fault Code F5

285 - 286 Secondary # Earth Fault Code F7

287 - 288 Secondary # Low Battery Fault Code F8

289 - 290 Secondary # No Battery Fault Code F9

291 - 292 Secondary # Telco Pri. Line Fault Code FA

293 - 294 Secondary # Telco Sec. Line Fault Code FB

295 - 296 Secondary # NAC #1 Fault Code FC

297 - 298 Secondary # NAC #2 Fault Code FC

299 - 300 Secondary # Comm Trouble Pri. # Code FD

301 - 302 Secondary # Comm Trouble Sec. # Code FE

303 - 304 Secondary # Annunciator Fault Code FC

305 - 306 Secondary # System Off Normal Code FF

307 - 308 Secondary # Zone 1 Alarm Restore Code E1

309 - 310 Secondary # Zone 2 Alarm Restore Code E2

311 - 312 Secondary # Zone 3 Alarm Restore Code E3

313 - 314 Secondary # Zone 4 Alarm Restore Code E4

315 - 316 Secondary # Zone 5 Alarm Restore Code E5

317 - 318 Secondary # Zone 1 Disable Restore Code E1

319 - 320 Secondary # Zone 2 Disable Restore Code E2

321 - 322 Secondary # Zone 3 Disable Restore Code E3

323 - 324 Secondary # Zone 4 Disable Restore Code E4

325 - 326 Secondary # Zone 5 Disable Restore Code E5

327 - 328 Secondary # Drill Restore Code 98

329 - 330 Secondary # AC Fault Restore Code E6

331 - 332 Secondary # Zone 1 Fault Restore Code E1

333 - 334 Secondary # Zone 2 Fault Restore Code E2

335 - 336 Secondary # Zone 3 Fault Restore Code E3

337 - 338 Secondary # Zone 4 Fault Restore Code E4

339 - 340 Secondary # Zone 5 Fault Restore Code E5

341 - 342 Secondary # Earth Fault Restore Code E7

343 - 344 Secondary # Low Battery Fault Restore Code E8

345 - 346 Secondary # No Battery Fault Restore Code E9

347 - 348 Secondary # Telco Pri. Line Fault Restore Code EA

349 - 350 Secondary # Telco Sec. Line Fault Restore Code EB

351 - 352 Secondary # NAC #1 Fault Restore Code EC

353 - 354 Secondary # NAC #2 Fault Restore Code EC

355 - 356 Secondary # Comm Trouble Pri. # Restore Code ED

357 - 358 Secondary # Comm Trouble Sec. # Restore Code EE

359 - 360 Secondary # Annunciator Fault Restore Code EC

361 - 362 Secondary # System Off Normal Restore Code EF

363 - 364 Secondary # System Test Report 99

365 - 366 Secondary # System Abnormal Test Report 91

367 - 368 Secondary # Request for Up/Download 71

369 - 370 Secondary # Successful Upload 72

371 - 372 Secondary # Successful Download 73

373 - 374 Secondary # Failed Up/Download 74