Fire-Lite MS5012 Basic Commands

This is a Fire system, powering down is usually illegal!

Zones 5 Fire Zones

Silence Alarm Press SILENCE

Reset System Press RESET (Display will show rES for 6 seconds)

Tech_201000002550.gif (Displays active alarm or 1st previous event)

Tech_201000002551.gif (Displays newest Alarms in memory)

Tech_201000002552.gif (Displays previous Alarms in memory)

Zone Disable (If zone is in trouble only)

  1. Press MODE (Display goes blank)

  2. Press 3472 + ENTER/STORE (Display shows "d")

  3. Enter Zone to disable (1 to 5) (Zone will appear at far right of display)

  4. Press ENTER/STORE (Trouble LED will blink, d__ 1 to 4 displays)

Zone Re-Enable (If zone was disabled with a trouble)

  1. Press MODE (Display goes blank)

  2. Press 3622 + ENTER/STORE (Display shows flashing "E")

  3. Enter Zone to re-enable (1 to 5) (Zone will appear at far right of display)

  4. Press ENTER/STORE (Trouble LED will turn OFF)

Fire Drill 1. Press MODE (Display goes blank)

2. Press 3745 + ENTER/STORE (Display shows "dril")

3. Press RESET to exit

Lamp Test MODE + 5267 + ENTER/STORE (turns on all System LED's for 5 seconds)

Walk Test 1. Press MODE (Display goes blank)

2. Press 9255 + ENTER/STORE (Trouble light begins blinking)

3. Press 6676 + ENTER/STORE to exit

History Mode 1. Press MODE (Display goes blank)

2. Press 4478 + ENTER/STORE

Tech_201000002551.gif Displays newest Alarms in History

Tech_201000002552.gif Displays previous Alarms in History

3. Press SILENCE twice to erase Alarm History

4. Press 6676 + ENTER/STORE to exit

Displays d__1 = Zone 1 Disabled F__4 = Trouble Zone 4

d__2 = Zone 2 Disabled F__5 = Trouble Zone 5

d__3 = Zone 3 Disabled F__A = Annunciator Fault

d__4 = Zone 4 Disabled F__E = Earth Fault

d__5 = Zone 5 Disabled Lo_b = Low Battery

E__1 = Zone 1 Enabled no_b = No Battery

E__2 = Zone 2 Enabled PH_1 = Primary C. S. Number Comm Fault

E__3 = Zone 3 Enabled PH_2 = Secondary C. S. Number Com Fault

E__4 = Zone 4 Enabled bEL1 = Bell 1 Fault or Disabled

E__5 = Zone 5 Enabled bEL2 = Bell 2 Fault or Disabled

A__1 = Alarm Zone 1 no_1 = Primary Phone Line Fault

A__2 = Alarm Zone 2 no_2 = Secondary Phone Line Fault

A__3 = Alarm Zone 3 SUP1 = Supervisory Alarm Zone 1

A__4 = Alarm Zone 4 SUP2 = Supervisory Alarm Zone 2

A__5 = Alarm Zone 5 SUP3 = Supervisory Alarm Zone 3

F__1 = Trouble Zone 1 SUP4 = Supervisory Alarm Zone 4

F__2 = Trouble Zone 2 SUP5 = Supervisory Alarm Zone 5

F__3 = Trouble Zone 3 _AC_ = AC Power Loss

rES_ = System Reset