Fire-Lite MS5024/5024E Program Sheet (Under Construction)

Enter Program 1. Press MODE (Display goes blank)

2. Within 10 seconds enter 7764 (Display will show numbers entered)

3. Press ENTER/STORE key (Display shows "00_ ", Trouble LED blinks)

("00_ " Is 1st location in programming and data in that location)

Program Keys Tech_201000002553.gif = Selects Operating Mode

Tech_201000002551.gif = Go to next Address (Location)

Tech_201000002552.gif = Go to previous Address

Tech_201000002550.gif = Press once to go to Address 00

Tech_201000002550.gif = Press twice then enter Address to go to then Tech_201000002554.gif

Tech_201000002554.gif = Saves Data and goes to next Address

Enter Data Enter data in each location (0 to F) + ENTER/STORE to save and move to next location

Exit Program MODE + 6676 + ENTER/STORE (Returns to Normal Mode)

Initiate Download MODE + 3696 + ENTER/STORE

Primary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Primary Format I A _I 0 = 4 + 1 Ademco Express Standard DTMF, 1400/2300 Ack

Location 16 1 = 4 + 2 Ademco Express Standard DTMF, 1400/2300 Ack

2 = 3 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

3 = 3 + 1 Expanded 1800 Hz Carrier 2300 Hz Ack

4 = 3 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

  1. = 3 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

  2. = 4 + 1 Standard 1800 Hz Carrier, 2300 Hz Ack

  3. = 4 + 1 Expanded 1800 Hz Carrier, 2300 Hz Ack

  4. = 4 + 1 Standard 1900 Hz Carrier, 1400 Hz Ack

  5. = 4 + 1 Expanded 1900 Hz Carrier, 1400 Hz Ack

A = 4 + 2 Standard 1800 Hz Carrier, 2300 Hz Ack

B = 4 + 2 Expanded 1800 Hz Carrier, 2300 Hz Ack

C = 4 + 2 Standard 1900 Hz Carrier, 1400 Hz Ack

D = 4 + 2 Expanded 1900 Hz Carrier, 1400 Hz Ack

E = Not Used

F = Not Used

Primary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 17 18 19 20

Primary 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 21 22 23 24

Primary Test Interval I 0 _I 0 = 24 Hours

Location 25 1 = 12 Hours

2 = 8 Hours

3 = 6 Hours

Secondary Phone Number

I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I _ _I _ _I _ _I _I

Location 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

A = * B = # C = Wait for Dial Tone

D = 3-second pause E = 5 second pause F = End of Phone Number

Secondary Format I A _I

Location 42

Secondary Account I _ _I _ _I _ _I _I 0 to 9, A to F

Location 43 44 45 46

Sec. 24Hr Test Time I 0 _I 2 _I 0 _I 0 _I 0000 to 2359

Location 47 48 49 50

Sec. Test Interval I 0 _I 0 = 24 Hours

Location 51 1 = 12 Hours

2 = 8 Hours

3 = 6 Hours

Alarm Verification I 0 _I 0 = No Verification

Location 52 1 = Verification (only for 2-wire Smokes)

Programmable Relay 1 I 1 _I 0 = Disable

Location 53 1 = Alarm

2 = Supervisory

Programmable Relay 2 I 4 _I 3 = Alarm or Supervisory

54 4 = Trouble

5 = Alarm or Trouble

6 = Supervisory or Trouble

7 = Alarm or Supervisory or Trouble

8 = Communication Failure

9 = Alarm or Communication Failure

A = Supervisory or Communication Failure

B = Alarm or Supervisory or Communication Failure

C = Trouble or Communication Failure

D = Alarm or Trouble or Communication Failure

E = Supervisory or Trouble or Communication Failure

F = Alarm, Supervisory, Trouble, Communication Failure

For Future Use I _ _I

55

Slave Com,/Fire Panel I 2 _I 0 = Fire Panel only

Location 56 1 = Slave Communicator Only

2 = Fire Panel/Communicator

Zone 1 - 5 Function I 0 _I 0 _I 0 _I 0 _I 0 _I 0 = Operates 2-Wire Smoke Detector

Location 57 58 59 60 61 1 = Pull Station

Zone 1 2 3 4 5 2 = Normally Open Contact Device

3 = Supervisory

4 = Supervisory, Auto Resettable, Self

Restore function, not latched

5 = Waterflow, Silenceable, Silence of Silenceable

Notification Circuits Allowed, Affects Zone 3

Only

6 = Waterflow, non - silenceable, Silence of

Silenceable Notification Circuits Allowed,

Affects Zone 3 Only

Waterflow Retard Timer I 0 _I 0 _I 00 to 89 seconds

Location 62 63

AC Loss Report Delay I 0 _I 0 = 6 Hours 8 = 16 Hours

Location 64 1 = 7 Hours 9 = 17 Hours

2 = 8 Hours A = 18 Hours

3 = 9 Hours B = 19 Hours

4 = 10 Hours C = 20 Hours

5 = 11 Hours D = 21 Hours

6 = 12 Hours E = 22 Hours

7 = 15 Hours F = 23 Hours

Alarm Presignal I 0 _I 0 = No Presignal

Location 65 1 = Delay before transmission

Presignal Delay Timer I 1 _I 2 _I 0 _I 000 to 179 minutes

Location 66 67 68

Notification Appliance Circuit 1 Enable 0 = Silenceable

I 0 _I 1 = Non-Silenceable

Location 69 2 = Disabled

(2 causes "bEL2" to display & sounds piezo)

Silence inhibit Notification Circuit 1 0 = No silence inhibit

I 0 _I 1 = Prohibits silencing for 1 minute

Location 70

Auto Silence notification Notification Circuit 1 0 = No autosilence 4 = 20 minutes

I 0 _I 1 = 5 minute autosilence 5 = 25 minutes

Location 71 2 = 10 minutes 6 = 30 minutes

3 = 15 minutes

Coding, Notification Appliance Circuit 1 0 = Steady

I 0 _I 1 = March Time (120ppm)

Location 72 2 = California (10 sec ON, 5 sec OFF)

3 = Temporal (.5 sec ON, .5 sec OFF)

Notification Appliance Circuit 2 Enable 0 = Silenceable

I 0 _I 1 = Non-Silenceable

Location 73 2 = Disabled

(2 causes "bEL2" to display & sounds piezo)

Silence inhibit Notification Circuit 2 0 = No silence inhibit

I 0 _I 1 = Prohibits silencing for 1 minute

Location 74

Auto Silence notification Notification Circuit 2 0 = No autosilence 4 = 20 minutes

I 0 _I 1 = 5 minute autosilence 5 = 25 minutes

Location 75 2 = 10 minutes 6 = 30 minutes

3 = 15 minutes

Coding, Notification Appliance Circuit 2 0 = Steady

I 0 _I 1 = March Time (120ppm)

Location 76 2 = California (10 sec ON, 5 sec OFF)

3 = Temporal (.5 sec ON, .5 sec OFF)

Trouble Reminder I 0 _I 0 = Disabled

Location 77 1 = Trouble Reminder beep every 15 sec

after alarm, beep every 2 minutes

Annunciator/Printer Supervision 0 = No Annunciator or Printer

I 0 _I 1 = Annunciator present

Location 78 2 = Printer present

3 = Annunciator and Printer present

Backup Reporting I 0 _I 0 = Secondary Phone as Backup

Location 79 1 = All reports to Secondary Phone

TouchTone/Rotary I 0 _I 0 = TouchTone Dialing both Numbers

Location 80 1 = Rotary Dialing both Numbers

Make Break Ratio I 0 _I 0 = Make/Break Ratio 67/33

Location 81 1 = Make/Break Ratio 62/38

Report Codes (Leave at default!)

Address Description Default

82 - 83 Primary # Zone 1 Alarm Code 11

84 - 85 Primary # Zone 2 Alarm Code 12

86 - 87 Primary # Zone 3 Alarm Code 13

88 - 89 Primary # Zone 4 Alarm Code 14

90 - 91 Primary # Zone 5 Alarm Code 15

92 - 93 Primary # Zone 1 Disable Code F1

94 - 95 Primary # Zone 2 Disable Code F2

96 - 97 Primary # Zone 3 Disable Code F3

98 - 99 Primary # Zone 4 Disable Code F4

100 - 101 Primary # Zone 5 Disable Code F5

102 - 103 Primary # Drill Code 97

104 - 105 Primary # AC Fault Code F6

106 - 107 Primary # Zone 1 Fault Code F1

108 - 109 Primary # Zone 2 Fault Code F2

110 - 111 Primary # Zone 3 Fault Code F3

112 - 113 Primary # Zone 4 Fault Code F4

114 - 115 Primary # Zone 5 Fault Code F5

116 - 117 Primary # Earth Fault Code F7

118 - 119 Primary # Low Battery Fault Code F8

120 - 121 Primary # No Battery Fault Code F9

122 - 123 Primary # Telco Pri. Line Fault Code FA

124 - 125 Primary # Telco Sec. Line Fault Code FB

126 - 127 Primary # NAC #1 Fault Code FC

128 - 129 Primary # NAC #2 Fault Code FC

130 - 131 Primary # Comm Trouble Pri. # Code FD

132 - 133 Primary # Comm Trouble Sec. # Code FE

134 - 135 Primary # Annunciator Fault Code FC

136 - 137 Primary # System Off Normal Code FF

138 - 139 Primary # Zone 1 Alarm Restore Code E1

140 - 141 Primary # Zone 2 Alarm Restore Code E2

142 - 143 Primary # Zone 3 Alarm Restore Code E3

144 - 145 Primary # Zone 4 Alarm Restore Code E4

146 - 147 Primary # Zone 5 Alarm Restore Code E5

148 - 149 Primary # Zone 1 Disable Restore Code E1

150 - 151 Primary # Zone 2 Disable Restore Code E2

152 - 153 Primary # Zone 3 Disable Restore Code E3

154 - 155 Primary # Zone 4 Disable Restore Code E4

156 - 157 Primary # Zone 5 Disable Restore Code E5

158 - 159 Primary # Drill Restore Code 98

160 - 161 Primary # AC Fault Restore Code E6

162 - 163 Primary # Zone 1 Fault Restore Code E1

164 - 165 Primary # Zone 2 Fault Restore Code E2

166 - 167 Primary # Zone 3 Fault Restore Code E3

168 - 169 Primary # Zone 4 Fault Restore Code E4

170 - 171 Primary # Zone 5 Fault Restore Code E5

172 - 173 Primary # Earth Fault Restore Code E7

174 - 175 Primary # Low Battery Fault Restore Code E8

176 - 177 Primary # No Battery Fault Restore Code E9

178 - 179 Primary # Telco Pri. Line Fault Restore Code EA

180 - 181 Primary # Telco Sec. Line Fault Restore Code EB

182 - 183 Primary # NAC #1 Fault Restore Code EC

184 - 185 Primary # NAC #2 Fault Restore Code EC

186 - 187 Primary # Comm Trouble Pri. # Restore Code ED

188 - 189 Primary # Comm Trouble Sec. # Restore Code EE

190 - 191 Primary # Annunciator Fault Restore Code EC

192 - 193 Primary # System Off Normal Restore Code EF

194 - 195 Primary # System Test Report 99

196 - 197 Primary # System Abnormal Test Report 91

Address Description Default

198 - 199 Secondary # Zone 1 Alarm Code 11

200 - 201 Secondary # Zone 2 Alarm Code 12

202 - 203 Secondary # Zone 3 Alarm Code 13

204 - 205 Secondary # Zone 4 Alarm Code 14

206 - 207 Secondary # Zone 5 Alarm Code 15

208 - 209 Secondary # Zone 1 Disable Code F1

210 - 211 Secondary # Zone 2 Disable Code F2

212 - 213 Secondary # Zone 3 Disable Code F3

214 - 215 Secondary # Zone 4 Disable Code F4

216 - 217 Secondary # Zone 5 Disable Code F5

218 - 219 Secondary # Drill Code 97

220 - 221 Secondary # AC Fault Code F6

222 - 223 Secondary # Zone 1 Fault Code F1

224 - 225 Secondary # Zone 2 Fault Code F2

226 - 227 Secondary # Zone 3 Fault Code F3

228 - 229 Secondary # Zone 4 Fault Code F4

230 - 231 Secondary # Zone 5 Fault Code F5

232 - 233 Secondary # Earth Fault Code F7

234 - 235 Secondary # Low Battery Fault Code F8

236 - 237 Secondary # No Battery Fault Code F9

238 - 239 Secondary # Telco Pri. Line Fault Code FA

240 - 241 Secondary # Telco Sec. Line Fault Code FB

242 - 243 Secondary # NAC #1 Fault Code FC

244 - 245 Secondary # NAC #2 Fault Code FC

246 - 247 Secondary # Comm Trouble Pri. # Code FD

248 - 249 Secondary # Comm Trouble Sec. # Code FE

250 - 251 Secondary # Annunciator Fault Code FC

252 - 253 Secondary # System Off Normal Code FF

254 - 255 Secondary # Zone 1 Alarm Restore Code E1

256 - 257 Secondary # Zone 2 Alarm Restore Code E2

258 - 259 Secondary # Zone 3 Alarm Restore Code E3

260 - 261 Secondary # Zone 4 Alarm Restore Code E4

262 - 263 Secondary # Zone 5 Alarm Restore Code E5

264 - 265 Secondary # Zone 1 Disable Restore Code E1

266 - 267 Secondary # Zone 2 Disable Restore Code E2

268 - 269 Secondary # Zone 3 Disable Restore Code E3

270 - 271 Secondary # Zone 4 Disable Restore Code E4

272 - 273 Secondary # Zone 5 Disable Restore Code E5

274 - 275 Secondary # Drill Restore Code 98

276 - 277 Secondary # AC Fault Restore Code E6

278 - 279 Secondary # Zone 1 Fault Restore Code E1

280 - 281 Secondary # Zone 2 Fault Restore Code E2

282 - 283 Secondary # Zone 3 Fault Restore Code E3

284 - 285 Secondary # Zone 4 Fault Restore Code E4

286 - 287 Secondary # Zone 5 Fault Restore Code E5

288 - 289 Secondary # Earth Fault Restore Code E7

290 - 291 Secondary # Low Battery Fault Restore Code E8

292 - 293 Secondary # No Battery Fault Restore Code E9

294 - 295 Secondary # Telco Pri. Line Fault Restore Code EA

296 - 297 Secondary # Telco Sec. Line Fault Restore Code EB

298 - 299 Secondary # NAC #1 Fault Restore Code EC

300 - 301 Secondary # NAC #2 Fault Restore Code EC

302 - 303 Secondary # Comm Trouble Pri. # Restore Code ED

304 - 305 Secondary # Comm Trouble Sec. # Restore Code EE

306 - 307 Secondary # Annunciator Fault Restore Code EC

308 - 309 Secondary # System Off Normal Restore Code EF

310 - 311 Secondary # System Test Report 99

312 - 313 Secondary # System Abnormal Test Report 91