Radionics D2112 Program Sheet Click HERE for Program Keys

Power Ratings 350mA Aux output

  1. 5A Siren output

Formats Modem IIIa2, 4x2

Download Info Answering Machine bypass must be ON

  1. Call panel with standard phone, wait for one or two rings, hangup and wait 30 seconds

  2. Call panel with standard phone, wait for one or two rings, hangup and wait 30 seconds

  3. Call panel with downloader, panel should pick up

or

Press 2 + User or Installer Passcode

Enter Program 1. Close Standby switch on main board, keypad OK light should flash

2. Press 1, keypad should beep

3. Enter Installer Code (Default = 654321, if Protect America use 1010)

(If Customer uses a 4-digit Code then Installer Code is only 4-digits)

  1. If successful all Zone lights except Zone 4 will turn ON

  2. Press 8 to enter program mode, ON and Zone 1 Led will turn ON

Program Steps 1. Move to Program Group (1 to 13) by pressing Right Panic key

2. Use Number keys to select Location in Group (1 to 8), Zone light shows location

3. To view a Location press Middle Panic key, number lights will flash Value

4. Press Left Panic key to modify Location, Zone light will flash, enter data

5. Press Left Panic key again to save Location, Zone light will stop flashing

  1. Use Number keys to select next Location or Right Panic for next Group

Delete Location Press CLEAR while in a Location

Hex Program While modifying a Location C+2=A, C+3=B, C+4=C, C+5=D, C+6=E, C+7=F

Exit Program Press CLEAR key, all Zone lights except 4 will turn ON, unclip Standby Switch

(System will now send a Reboot (R14) signal)

4/2 Signals Zone 1 31 Successful Download 81

Zone 2 32 Restore after Com Fail 82

Zone 3 33 Panel Reset Standby Sw 83

Zone 4 34 Aux Power/Fuse Restore 84

Zone 5 35 Siren Trouble/Fuse Restore 85

Zone 6 35 Missing Battery Restore 86

Zone 7 37 Low Battery Restore 87

Zone 8 38 AC Failure Restoral 88

Smoke Alarm 11 to 18 Cancel D1 to D8

Smoke Trouble 61 to 68 Unsuccessful Download 71

Keypad Fire Panic 91 Automatic Test Timer 72

Keypad Medical Panic 92 Automatic Reset 73

Keypad Police Panic 93 Aux Power Trouble/Fuse Open 74

6 wrong Codes entered 94 Siren Trouble/Fuse Open 75

Duress 95 Missing Battery Trouble 76

Opening 5 + User Low Battery 77

Closing 4 + User AC Failure 78

Part ON Arming (Closing) 50

All ON Arming (Closing) 40

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002138.gif

  1. Account Group

  1. Account (4-digits) I _ _I _ _I _ _I _ _I

  2. Phone 1 (19 digits) I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I

  3. Phone 2 (19 digits) I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I

  4. Download Phone I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I _ _I

  5. Download Passcode I _9 _I _9 _I _9 _I _9 _I _9 _I _9 _I

  6. Installer Code I _6 _I _5 _I _4 _I _3 _I _2 _I _1 _I

  7. Account Group Lock I _0 _I 0 = No

(Prevents keypad programming of Account) 1 = Yes

  1. Return to Default I _0 _I 0 = No

(Defaults Panel) 1 = Yes

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002139.gif

2. Phone Group

  1. DTMF Dialing I _1 _I 0 = No

  1. = Yes

  2. Answer w/Armed* I _5 _I Rings 5 times if Armed

  3. Answer w/Disarmed* I 15_I Rings 15 times if Disarmed

  4. Answer Machine I _1 _I 0 = No

  1. = Yes

*Locations 2 and 3 are disabled if Location 4 = Yes)

  1. Program Lock I _0 _I 0 = No (Always use No!)

(Prevents programming by keypad) 1 = Yes

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002140.gif

3. Receiver Format Group

  1. Receiver Format I _0 _I 0 = Pulse 4/2 format

  1. = Modem IIIa2 format

  2. Fire Group I _1 _I 1st digit of Report for Fire Points/Zones

  3. Non-Fire Group I _3 _I 1st digit of Report for Non-Fire Points/Zones

  4. Point Trouble Group I _6 _I 1st digit of Report for Trouble/Bypass/Swinger Points/Zones

  5. Restoral Group I _0 _I 1st digit of Report for Fire/Non Fire Points/Zones

  6. Closing Group I _0 _I 1st digit of Closing Report, if needed use 4

  7. Opening Group I _0 _I 1st digit of Opening Report, if needed use 5

  8. Cancel Group I _0 _I 1st digit of Cancel Report for Users 1 to 8

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002141.gif

4 . Report Group for Pulse

  1. Sys Trbl Group I _7 _I 1 = Unsuccessful Download Attempt

  2. = Automatic Test Timer Report

You program 1st digit here, panel 3 = Automatic Reset

sends it + what is listed to the right 4 = Short on Terminal 9, Aux Power, Fuse Open

(Ex: Low Battery trouble sends 77) 5 = Short on Terminal 6, Alarm Output, Fuse Open

6 = Report Battery Missing

7 = Report Low Battery

8 = No AC Power

2 Sys Restore Group I _8 _I 1 = Successful Download Attempt

2 = Successful Communication after Com Failure

You program 1st digit here, panel 3 = Panel Reset with Stand-By Switch

sends it + what is listed to the right 4 = Short Removed from Terminal 9, Aux Power Rest

(Ex: Low Battery Restore sends 87) 5 = Short Removed from Terminal 6, Alarm Output

6 = Not Used

7 = Report Missing or Low Battery Restoral

8 = AC Power Restoral

  1. Duress Rep Code I _9 _I 1 to 3 = Not used

  2. = Duress after 6 invalid Passcode attempts

  3. = Duress Code is User 8

  4. to 9 = Not used

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002142.gif

5. Reports Group Underlined = Default

  1. Delay Alarm Reports I _0 _I 0 = Disabled

  1. to 255 second delay before dial

  2. Cancel Report I _0 _I 0 = No

(If needed use D) 1 = Yes

  1. Restoral Reports I _0 _I 0 = No

  1. = Yes

4 Delay Rest Reports I _0 _I 0 = No

  1. = Yes

5 AC Fail Buzz/Reports I _2 _I 0 = No Buzzer or Report on AC Fail

  1. = Buzzer no Report

  2. = Buzzer and Report

  3. = Buzzer, Tag-Along Report

(Sends with next Alarm/Trouble)

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002143.gif

6. System Options Group Underlined = Default

  1. Disable System I _0 _I 0 = No

(Can only re-enable by 5200, DO NOT USE) 1 = Yes

  1. Excursion I _3 _I 0 = Disabled

  1. = All Inst

  2. = Part Inst

  3. = All & Part

3 Keyswitch I _0 _I 0 = Momentary

  1. = Easikey, Momentary

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002144.gif

7. Open Close Group

  1. Entry Delay Time I 30_I 0 to 255 seconds

  2. Exit Delay Time I 60_I 0 to 255 seconds

  3. Exit Tone I _1 _I 0 = No

  1. = Yes

4 Op/CL Rep ALL On I _0 _I 0 = No

(Open/Close Report if ALL (9) armed) 1 = Yes

5 Op/Cl Rep PART On I _0 _I 0 = No

(Open/Close Report if PART (0) armed) 1 = Yes

6 Restricted Op/Close I _0 _I 0 = No

(Opening Report if disarmed after alarm) 1 = Yes

7 Bell Test (on Arm) I _0 _I 0 = No

  1. = Yes

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002145.gif

8. A B C Keys Group

  1. A Key Report (Police) I 93_I 00 to 99

  2. B Key Report (Medical) I 92_I 00 to 99

  3. C Key Report (Fire) I 91_I 00 to 99

  4. A (Police) Panic Output I _1 _I 0 = No Output

  1. = Steady Output

  2. = Pulsed Output

5 B (Medical) Panic Output I _0 _I 0 = No Output

  1. = Steady Output

  2. = Pulsed Output

6 C (Fire) Panic Output I _2 _I 0 = No Output

  1. = Steady Output

  2. = Pulsed Output

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002146.gif

9. Bell & Test Timer Group

  1. Bell Output Time I _6 _I 0 to 255 Minutes

  2. Single Ring I _1 _I 0 = Siren outputs with every alarm

  1. = 1 Siren output once for each zone alarm

3 Alarm on 2 Fail I _0 _I 0 = No

  1. = Alarm on 2 Failed Report Attempts

4 Test Interval I _0 _I 0 = Disabled

  1. = 1 Day

  2. = 7 Days

  3. = 28 Days

5 Hours to Next Test Rpt I _0 _I 0 to 23 Hours

6 Min to Next Test Rpt I _0 _I 0 to 59 Minutes

7 Defer Test Report I _0 _I 0 = No

(Will not send test if another signal occurs) 1 = Yes

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002147.gif

10. Point Codes Default

  1. Point 1 I _2 _I _6 _I _0 _I Most Common are

  2. Point 2 I _8 _I _8 _I _2 _I Delay Door = 892

  3. Point 3 I _8 _I _8 _I _2 _I Instant Door = 992

  4. Point 4 I _9 _I _8 _I _2 _I Motion Zone = 792

  5. Point 5 I _7 _I _8 _I _2 _I Fire (Verified) Zone = 260

  6. Point 6 I _7 _I _8 _I _2 _I Audible Panic Zone = 420

  7. Point 7 (D2112E only) I _7 _I _8 _I _1 _I Silent Panic Zone = 520

  8. Point 8 (D2112E only) I _7 _I _8 _I _1 _I Disabled Zone = 000

  1. st Digit = Zone Type

  1. = Fire Zone 6 = Delay Zone, Active only in ALL Arm

  2. = Fire Zone w/Verification 7 = Interior Follower/Motion Zone

  3. = Buzzer on Fault 8 = Delay Zone, active in ALL or PART Arm

  4. = 24 Hr Audible 9 = Instant Zone

  5. = 24 Hr Silent A = Keyswitch (Zones 2 to 6 only)

2nd Digit = Alarm Response

0 = No Response

  1. = Report Enabled

  2. = Report Enabled/Alarm Report Delay

  3. = Report Enable/Alarm Rep Dellay/Swinger Shutdown

  4. = Report Enabled/Swinger Shutdown

  5. = Alarm Output

  6. = Report Enabled/Alarm Output

  7. = Report Enabled/Alarm Report Delay/Alarm Output

  8. = Report Enabled/Alarm Report Delay/Swinger Shutdown/Alarm Output

  9. = Report Enabled/Swinger Shutdown/Alarm Output

3rd Digit = Special Point (Zone) Options

0 = Disabled

  1. = Trouble on Open

  2. = Trouble on Short

  3. = Trouble on Open or Short

  4. = Double Knock (2 Violations before Alarm)

  5. = Trouble on Open/Double Knock

  6. = Trouble on Short/Double Knock

  7. = Trouble on Open or Short/Double Knock

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002148.gif

11. Relays Default

  1. Relay 1 Func 1 I _0 _I 0 = No Relay Output

  2. Relay 1 Func 2 I _0 _I 1 = Alarm

  3. Relay 2 Func 1 I _0 _I 2 = Alarm Memory

  4. Relay 2 Func 2 I _0 _I 3 = Point Trouble

4 = Follow Point

  1. = Watch Tone

  2. = A, B, C Keys Steady Relay Output

  3. = A, B, C Keys Momentary Relay Output

  4. = A, B, C Keys Momentary Relay Output

  5. = Off with Passcode

  6. = Follow Alarm Output

  7. = Pulses during E/E if ALL ON, on until Disarm

  8. = Pulses during E/E if PART ON, on until Disarm

  9. = Activate 4 seconds if User Resets system

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002149.gif

12. Relay Parameter Group Requires D133 Relay Module

  1. Relay 1, Function 1 I _0 _I 0 = No Output/Disabled

  1. = Alarm

  2. Relay 1, Function 2 I _0 _I 2 = Alarm Memory

  3. = Point Trouble

3 Relay 2, Function 1 I _0 _I 4 = Follow Point

5 = Watch Tone

  1. Relay 2, Function 2 I _0 _I 6 = A B C Key (Steady Output)

7 = A B C Key (Pulsed Output)

8 = A B C Key (Momentary Output)

9 = Off with Passcode

10 = Follow Alarm Output

11 = All On

12 = Part On

13 = Reset

14 = AC Failure

15 = Battery Trouble

16 = Communication Fail

17 = Communicating

18 = Ground Start

  1. Relay 1 Logic I _0 _I 0 = Function 1 Only

  1. = Function 1 or 2

6 Relay 2 Logic I _0 _I 2 = Function 1 and 2

------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Tech_201000002150.gif

13. User Config Group

  1. User Test/Bell? I _1 _I 0 = No

  1. = Yes

  2. User Test/Battery? I _1 _I 0 = No

  1. = Yes

3 User Test/Comm? I _1 _I 0 = No

  1. = Yes

4 Passcode Length I _4 _I 3 = 3-Digit User Codes

4 = 4-Digit User Codes

5 = 5-Digit User Codes

6 = 6-Digit User Codes

5 User Code 8 is Duress I _1 _I 0 = No

  1. = Yes

6 Passcode Required I _0 _I 0 = No Code Required to Arm

  1. = Code Required to Arm

7 Change Passcode I _1 _I 0 = No User Code changing Allowed

  1. = Owner changes User Code

  2. = Owner or User changes User Code

14. Passcodes Group (Only available with 5200 Program or by Downloading!)

  1. User # Type Disabled/Owner/User/One-Time

  2. User # Passcode

D9 = Watchdog Reset

D14 = Reboot

R9 = Low Battery Restore

R0 = AC Restore

P = AC Failure

T9 = Battery Missing